OFF position (Default)  Default OFF position configures conventional mode, ON position enables Heat Pump mode  

 
Example 1: Conventional Two-Stage Cooling and Heating - 

Dipswitch 1-1 set to OFF position (default position)

 RMF-CA200-

V1 operates in dual stage heat / cool mode using thermostat signals W1, W2, Y1, Y2, and fan signal (G). G1, G2 and G3 are 
available but not required. 
 

 

Example 2: Single-Stage Operation- 

Dipswitch 1-1 set to ON position

 

If Y2 or W2 is left unconnected or is unavailable from the thermostat 
set SW1-1 to the ON position.

 This configures single stage operation of 

RMF-CA200-V1 simulating multiple stage operation using temperature 
differential based on W1 / Y1 call and run time. 

 

 

 

Example 3: Heat Pump Mode Operation - 

Dipswitch 1-1 set to ON position

 

If Y2 or W2 is left unconnected or is unavailable from the thermostat 
set SW1-1 to the ON position.

 This configures single stage operation of 

RMF-CA100-V1 simulating multiple stage operation using temperature 
differential based on W1 / Y1 call and run time. 

 

Conventional Mode Connector Pin Layout 

Pin Signal Description 

1 TC Common 

(IN) 

Transformer 

Common (Out) To Thermostat 

TR 

24 VAC (IN) Transformer 

24 VAC (IN) Thermostat 

Y2 

Stage 2 Cooling 

Y1 

Stage 1 Cooling 

W2 

Stage 2 Heat 

W1 

Stage 1 Heat 

W3 

Stage 3 Heat 

10 G Fan 

11 

Stage 4 Heat 

12 EO Error 

Output 

(Out) 

In

 

single

 

stage

 

operation

 

Y2,

 

W2

 

and

 

W3

 

signals

 

are

 

not

 

used.

 