ELECTRICAL WIRING
9-1. OVERVIEW OF POWER WIRING
9-2. WIRE DIAMETER AND MAIN POWER SWITCH CAPACITY
9-2-1. Wiring diagram for main power supply
9-2-2. Power supply wire diameter and capacity
This chapter provides an introduction to electrical wiring for the MULTI-S series, together with notes concerning power wiring,
wiring for control (transmission wires and remote controller wires), and the frequency converter.
(1) Please refer to your electric power company about the indoor wiring specifications for the power wire diameter
and capacity of protective devices (switches and leakage of breakers).
(2) Taking into consideration voltage drops caused by the length of the wires when operating devices installed
downstream, determine the specifications of wires able to handle the maximum current or voltage. In addition,
protective devices must be able to protect against current leakage or excessive current.
(3) It is generally necessary to include leakage breakers when installing wiring for the Mr. SLIM MULTI-S series.
Protective switches (excessive current protection) along main or branch lines should typically consist of fuseless
breakers (ELB).
(4) Please perform grounding.
(5) It is suggested that you consult with your electric power company concerning restrictions on electrical specifications.
Outdoor unit
Indoor unit
Grounded
Grounded
Junction box
Circuit breaker
N
Power supply
MODEL : PUMY-VM(A)
(single phase 220-230-240V, 50Hz)
(single phase 220V, 60Hz)
MODEL : PUMY-YM(A)
(3phase 380-400-415V, 50Hz)
(3phase 380V, 60Hz) : YM
1
only
Circuit breaker
Power supply
single phase
50Hz 220-230-240V
single phase
60Hz 220V
Interrupting current
30A
100A
25A
32A
Grounded
3.5
5.5
2.5
5.5(6)
Minimum wire cross section area(mm
2
)
Breaker
Model
Branch line
—
—
—
—
Main line
5.5
14
2.5
5.5(6)
PUMY-71VM
PUMY-71VM
1
PUMY-125VM
PUMY-125VM
1
PUMY-125VM
2
PUMY-125YM
PUMY-125YM
1
PUMY-125YMA
PUMY-125VMA
PUMY-125VMA
1
Performance characteristic
30A,30mA for 0.1 sec. or less
100A,100mA for 0.1 sec. or less
25A,30mA for 0.1 sec. or less
32A,30mA for 0.1 sec. or less
Outdoor unit
Interrupting current
15A
Grounded
[
1.6
Minimum wire cross section area(mm)
Breaker
Model
Branch line
–
Main line
[
1.6
All Models
Performance characteristic
15A, 30mA for 0.1 sec. or less
Indoor unit
OC183E--4.qxp 10.5.6 0:54 PM Page 103