24
OPERATING PROCEDURE
PHOTOS&ILLUSTRATIONS
2. Removing the electrical parts box
(1) Remove the panel.
(2) Remove the cover.
(3) Remove the electrical parts cover.
(4) Disconnect the connectors of fan motor, vane motor, drain
pump, room temperature thermistor, pipe temperature
thermistor, condenser/evaporator temperature thermistor
and drain sensor on the electrical controller board.
(5) Disconnect the lead wire and earth wire from terminal
block.
(6) Remove tne electrical parts box.
3. Removing the stabilizer
(1) Remove the panel.
(2) Remove the room temperature thermistor.
(3) Unhook the claw in the middle of stabilizer and remove
the drain pan. (5 screws) (See photo 2)
(4) Remove the stabilizer side of the heat exchanger. (2 screws)
(5) Remove the cover.
(6) Remove the electrical parts cover.
(7) Disconnect the connector of vane motor.
(8) Remove the insulation material (white) on the right side of
stabilizer.
(9)Remove the stabilizer. (6 screws)
·Since the insulation material (white) which prevents water-
drops from putting is mounted to the side of vane
motor,remove the insulation material when the stabilizer is
removed.(See figure 4)
·After completing the service, mount the insulation material
as before as shown in right figure.
·Since the insulation material to prevent water-drops from
putting consists of double layer of soft and hard materials,
mount the insulation material so that the hard material
faces to the stabilizer side.
Note when the stabilizer is removed
4. Removing the vane motor
(1) Remove the stabilizer. Refer to above-mentioned (3)
Removing the stabilizer.
(2) Remove the vane motor.
Photo 5
Photo 4
Photo 3
Photo 2
Vane motor
Stabilizer
Vane motor
Stabilizer
Drain pan
Hard material Insulation material
Electrical parts
Soft material
Room temperature thermistor
Stabilizer
Claw in middle
of stabilizer
cover
Figure 4
Heat exchanger
Electrical parts
cover