45
44
OPERATING PROCEDURE
PHOTOS
4. Removing the room temperature thermistor (TH1)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connector CN20 (Red) from the indoor
controller board.
(3) Remove the room temperature thermistor with its
holder. (See Photo 4)
5. Removing the indoor controller board (I.B)
(1) Remove the electrical box cover. (See Photo 1 and 2)
(2) Disconnect the connectors:
CNMF (White) for fan motor
CNV (White) for vane motor
CN5Y (White) for motor for i-see Sensor (Option)
CN4Z (White) for sensor for i-see Sensor (Option)
CN90 (White) for signal receiver (Option)
CNP (White) for drain pump
CN4F (White) for float switch
CN44 (White) for thermistor (TH2/TH5)
CN01 (Black) for Indoor/Outdoor connecting line
CN3C (Blue) for Indoor/Outdoor transmission
Disconnect the connectors for optional parts, if any.
(3) For the unit controlled with the wireless remote control
-
ler, disconnect the lead wire connected to TB5 on the
indoor controller board.
TB5: Remote controller transmission connecting wire
(4) Remove the indoor controller board (3 holders/4 Hooks).
(See Photo 5)
Indoor controller
board
Electrical box
CN20
Electrical box
fixing screw
(M5×10)
Electrical box
fixing screw
(M5×10)
Photo 3
Thermistor holder
Holders
Hooks
Photo 5
Thermistor (TH1)
Room temperature thermistor (TH1)
Photo 4
OCH650
Содержание PLA-ZM100EA.UK
Страница 49: ...49 OCH650...