11
Cooling
32,100
9,400
3.59
0.11
0.52
0.90
Heating
36,800
10,800
3.77
0.11
0.52
0.90
Single phase, 50Hz, 220-230-240V
Munsell 3.4Y 7.7/0.8
Plate fin coil
Line flow (direct) x 2
0.070
22-28(775-990)
0(direct blow)
Wireless remote controller & built-in
41-46
26(1)
1,680(66-1/8)
235(9-1/4)
340(13-3/8)
28(62)
PKA-RP4FAL
PKA-RP4FAL
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K
/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan
Fan(drive) x No.
Fan motor output
Airflow(Low-High)
External static pressure
Operation control & Thermostat
Noise level(Low-High)
Unit drain pipe O.D.
Dimensions
Weight
W
D
H
INDOOR UNIT
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F)
Outdoor
: D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor
: D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
4. Above data based on indicated voltage
Indoor Unit Single phase 230V 50Hz
Outdoor Unit 3 phase 400V 50Hz
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C, W.B. 22.5˚C
D.B. 19˚C, W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C, W.B. 18˚C
D.B. -11˚C, W.B. -12˚C
Cooling
Heating
Service Ref.
OUTDOOR
UNIT
5. Refer to the service manual of outdoor unit for the outdoor unit's specifications.
3. Guaranteed voltage
198~264V, 50Hz
PUH-P4YGAA
PUH-P4VGAA.UK / PUH-P4YGAA.UK
PUH-P4VGAA
1
.UK / PUH-P4YGAA
1
.UK
OC301B--1.qxp 13.8.20 3:16 PM Page 11
OC301B