SAFETY PRECAUTION

2

Cautions for units utilising refrigerant R410A

2-2. CAUTIONS RELATED TO NEW REFRIGERANT

Use new refrigerant pipes.

Make sure that the inside and outside of refrige-

rant piping is clean and it has no contamination

such as sulfur hazardous for use, oxides, dirt, 

shaving particles, etc.

In addition, use pipes with specified thickness.

In case of using the existing pipes for R22, be careful with

the following:

· For RP100, 125 and 140, be sure to perform replace-

  ment operation before test run.

· Change flare nut to the one provided with this product. 

  Use a newly flared pipe. 

· Avoid using thin pipes.

Charge refrigerant from liquid phase of gas

cylinder.

If the refrigerant is charged from gas phase, composition 

change may occur in refrigerant and the efficiency will be 

lowered.

Do not use refrigerant other than R410A.

If other refrigerant (R22, etc.) is used, chlorine in refrige-

rant can cause deterioration of refrigerant oil, etc.

Use a vacuum pump with a reverse flow check 

valve.

Vacuum pump oil may flow back into refrigerant cycle and 

that can cause deterioration of refrigerant oil, etc.

Use the following tools specifically designed for 

use with R410A refrigerant.

The following tools are necessary to use R410A refrigerant.

Handle tools with care.

If dirt, dust or moisture enters into refrigerant cycle, that can

cause deterioration of refrigerant oil or malfunction of com-

pressor.

Do not use a charging cylinder.

If a charging cylinder is used, the composition of refrigera-

nt will change and the efficiency will be lowered.

Flare tool

Electronic refrigerant 

charging scale

Vacuum pump adaptor

Size adjustment gauge

Gauge manifold

Torque wrench

Gas leak detector

Charge hose

Tools for R410A

Contamination inside refrigerant piping can cause deterio-

ration of refrigerant oil, etc.

Ventilate the room if refrigerant leaks during 

operation. If refrigerant comes into contact with

a flame, poisonous gases will be released.

Use the specified refrigerant only.

Never use any refrigerant other than that specified.

Doing so may cause a burst, an explosion, or fire when the 

unit is being used, serviced, or disposed of.

Correct refrigerant is specified in the manuals and on the 

spec labels provided with our products.

We will not be held responsible for mechanical failure, 

system malfunction, unit breakdown or accidents caused 

by failure to follow the instructions.

Store the piping indoors, and both ends of the 

piping sealed until just before brazing. 

(Leave elbow joints, etc. in their packaging.)

If dirt, dust or moisture enters into refrigerant cycle, that can 

cause deterioration of refrigerant oil or malfunction of compressor.

The refrigerant oil applied to flare and flange

connections must be ester oil, ether oil or 

alkylbenzene oil in a small amount.

If large amount of mineral oil enters, that can cause deterio-

ration of refrigerant oil, etc.

2-1. ALWAYS OBSERVE FOR SAFETY

Before obtaining access to terminal, all supply 

circuits must be disconnected.

OCH452B

Содержание PKA-RP100KALR1.TH

Страница 1: ...N OFF TEMP PARTS CATALOG OCB452 INDOOR UNIT PKA RP60KAL TH PKA RP60KAL TH ER PKA RP60KALR1 TH PKA RP60KALR1 TH ER PKA RP71KAL TH PKA RP71KAL TH ER PKA RP71KALR1 TH PKA RP71KALR1 TH ER PKA RP100KAL TH...

Страница 2: ...ZRP60 71VHA PUHZ RP35 50 60 71VHA4 PUHZ RP100 125 140VKA PUHZ RP100 125 140 200 250YKA PU H P71 100VHA PU H P71 100 125 140YHA PUHZ HRP100VHA2 PUHZ HRP100YHA2 PUHZ ZRP100VKA2 UK PUHZ ZRP100YKA2 UK PUH...

Страница 3: ...com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scal...

Страница 4: ...rse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1...

Страница 5: ...isplays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has been...

Страница 6: ...46 kW A kW K min CFM Pa mmAq kW dB mm in mm in mm in mm in kg lb Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive o No Fan motor output A...

Страница 7: ...20 230 240V 50Hz 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 0 55 0 60 0 65 0 70 0 63 125 250 500 1k 2k 4k 8k NC 60 NC 50 Octave band pressure level dB 0dB 20 Pa Approximate minimum audible limit on co...

Страница 8: ...T STAND BY lamp Receiver Knockout hole for right piping Mount board Right side 444 Gas pipe 482 Liquid pipe 585 Drain hose Filter hook Under side Vane auto Knockout hole for lower piping Louver manual...

Страница 9: ...te controller transmission line TB6 TH2 SW1 TH5 SW2 SWE LEGEND TO OUTDOOR UNIT 5 3 1 3 1 CN01 BLK ORN YLW BLU RED GRN YLW I B w1 Fig 1 I B TB2 POWER SUPPLY 1PHASE 230V 50Hz ORN ORN YLW BRN TB4 INDOOR...

Страница 10: ...low in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 8 PKA RP60KAL TH PKA RP71KAL TH PKA RP10...

Страница 11: ...ording to 9 4 TROUBLESHOOTING BY INFERIOR PHENOMENA The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as the work of protection devices in the refrigerant circuit i...

Страница 12: ...s cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote control...

Страница 13: ...Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Dr...

Страница 14: ...sible due to system start up Correct operation Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Inc...

Страница 15: ...heck resistance value of thermistor For characteristics refer to P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 9 7 TEST POINT DIAGRAM Turn the power on and...

Страница 16: ...or fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass circuit of outdoor...

Страница 17: ...Set one of the remote controllers main if there is no problem with the action above 3 Check wiring of remote controller Total wiring length max 500m Do not use cable 3 or more The number of connecting...

Страница 18: ...ler circuit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1...

Страница 19: ...ouble 2 Drain defective Drain pump clogging Drain pipe clogging 3 Open circuit of float switch 4 Contact failure of float switch connector 5 Dew condensation on float switch Drain water descends along...

Страница 20: ...al block S1 and S2 When 220 240 V AC is not detected check indoor outdoor unit connecting wire for miswiring When 220 240 V AC is detected check 4 below 4 Check the fuse on indoor controller board Che...

Страница 21: ...k the connection of remote controller wires in the case of twin triple indoor unit system When 2 or more indoor units are wired in one refrigerant system connect remote controller wires to one of thos...

Страница 22: ...unit operates as follows 1 Indoor fan is running at high speed 2 Drain pump is operating Note on the wireless remote control When the remote control does not function it is possible to activate Emerg...

Страница 23: ...llow 1 Brown Orange 3 Green 5 Connect pin No M Refer to 9 6 2 DC Fan motor fan motor indoor controller circuit board 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperatur...

Страница 24: ...VDC 310 340 V DC TEST POINT 2 VCC between 4 and 3 of the fan connector VCC 15 V DC Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replac...

Страница 25: ...re J41 J42 Pair No setting for wireless remote controller CN01 Connect to the Terminal block TB4 1 3 220 240 V AC LED1 Power supply I B LED2 Power supply R B LED3 Transmission Indoor outdodr CN3C Tran...

Страница 26: ...The pair number settings of the wireless remote controller and indoor control PCB J41 J42 are given in the table on the left in the table indicates the jumper wire is disco nnected Marks in the table...

Страница 27: ...d Back up function Outline of functions Main and sub unit operate alternately according to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch se...

Страница 28: ...itoring the request code of current setting Setting contents Rotation ON Alternating interval 28days and back up function Rotation ON Alternating interval 14days and back up function Rotation ON Alter...

Страница 29: ...en D when Maintenance monitor is activated The display D now allows you to set a request code No 4 Press the TEMP and buttons 4 to select the desired refrigerant address 5 Press the CLOCK and buttons...

Страница 30: ...tors on the indoor controller board See Photo 3 4 Remove the switch board holder and open the cover 5 Pull out the indoor controller board toward you then remove the indoor controller board and switch...

Страница 31: ...r to 1 2 Remove the electrical box covers Refer to 2 3 Disconnect the vane motor connector CN151 on the indoor controller board 4 Pull out the drain hose from the nozzle assembly and remove nozzle ass...

Страница 32: ...eat exchanger See Photo 9 10 Lift the heat exchanger and pull out the line flow fan to the lower left Photo 7 7 Removing the pipe temperature thermistor liquid TH2 and cond eva temperature thermistor...

Страница 33: ...f the heat exchanger See Photo 9 7 Remove the heat exchanger 9 Removing the room temperature thermistor 1 Remove the panel and corner box Refer to 1 2 Remove the electrical box covers 3 Remove the roo...

Страница 34: ...2009 MITSUBISHI ELECTRIC CORPORATION Distributed in Jul 2014 No OCH452 REVISED EDITION B Distributed in May 2011 No OCH452 REVISED EDITION A Distributed in Feb 2009 No OCH452 PDF 6 Made in Japan New...

Отзывы: