background image

16

Check code

Abnormal point and detection method 

Cause

Countermeasure

P6

Freezing/overheating protection is oper-

ating

1

 Freezing protection (Cooling mode)

The unit is in 6-minute resume preven-

tion mode if pipe <liquid or condenser/

evaporator> temperature stays under 

−15

:

 for 3 minutes, 3 minutes after the 

compressor started. Abnormal if it stays 

under −15

:

 for 3 minutes again within 

16 minutes after 6-minute resume pre-

vention mode.

2

 Overheating protection (Heating mode)

The unit is in 6-minute resume 

prevention mode if pipe <liquid or con

-

denser/evaporator> temperature is 

detected as over 70

:

 after the com-

pressor started. Abnormal if the tem-

perature of over 70

:

 is detected again 

within 30 minutes after 6-minute resume 

prevention mode.

P8

1

 Slight temperature difference 

between indoor room 

temperature and pipe <liquid 

or condenser / evaporator> 

temperature thermistor

• Shortage of refrigerant

• Disconnected holder of 

pipe <liquid or condenser / 

evaporator> thermistor

• Defective refrigerant circuit

2

 Converse connection of 

extension pipe (on plural units 

connection)

3

 Converse wiring of indoor/

outdoor unit connecting wire 

(on plural units connection)

4

 Defective detection of indoor 

room temperature and pipe 

<condenser / evaporator> 

temperature thermistor

5

 Stop valve is not opened 

completely.

(Cooling or drying mode)

1

 Clogged filter (reduced airflow)

2

 Short cycle of air path

3

 Low-load (low temperature) 

operation out of the tolerance 

range

4

 Defective indoor fan motor

 • Fan motor is defective.

 • Indoor controller board is defec

-

tive.

5

 Defective outdoor fan control

6

 Overcharge of refrigerant

7

 Defective refrigerant circuit 

(clogs)

(Heating mode)

1

 Clogged filter (reduced airflow)

2

 Short cycle of air path

3

 Over-load (high temperature) 

operation out of the tolerance 

range

4

 Defective indoor fan motor

 • Fan motor is defective.

 • Indoor controller board is defec

-

tive.

5

 Defective outdoor fan control

6

 Overcharge of refrigerant

7

 Defective refrigerant circuit 

(clogs)

8

 Bypass circuit of outdoor unit 

is defective. 

(Cooling or drying mode)

1

 Check clogs of the filter.

2

 Remove shields.

4

 Refer to "9-6 HOW TO CHECK THE 

PARTS"

5

 Check outdoor fan motor. 

67

  Check operating condition of refrigerant 

 

 circuit.

(Heating mode)

1

 Check clogs of the filter.

2

 Remove shields.

4

 Refer to "9-6 HOW TO CHECK THE 

PARTS"

5

 Check outdoor fan motor. 

6

8

Check operating condition of refrigerant 

circuit.

Pipe temperature

<Cooling mode>

Detected as abnormal when the pipe tem-

perature is not in the cooling range 3 min

-

utes after compressor start and 6 minutes 

after the liquid or condenser/evaporator 

pipe is out of cooling range.

Note 1: It takes at least 9 minutes to 

detect.

Note 2: Abnormality P8 is not detected in 

drying mode.

Cooling range : −3°C 

(TH−TH1) 

TH: Lower temperature between liquid pipe 

temperature (TH2) and condenser/

evaporator temperature (TH5)

TH1: Intake temperature 

<Heating mode>

When 10 seconds have passed after the 

compressor starts operation and the hot 

adjustment mode has finished, the unit is 

detected as abnormal when condenser/

evaporator pipe temperature is not in heat-

ing range within 20 minutes. 

Note 3: It takes at least 27 minutes to 

detect abnormality.

Note 4: It excludes the period of defrosting. 

(Detection restarts when defrosting 

mode is over.)

Heating range: 3°C 

(TH5−TH1)  

1

Check pipe <liquid or condenser / evapo

-

rator> temperature with room tempera-

ture display on remote controller and 

outdoor controller circuit board.

 

Pipe <liquid or condenser / evaporator> 

temperature display is indicated by set-

ting SW2 of outdoor controller circuit 

board as follows.

23

Check converse connection of extension 

pipe or converse wiring of indoor/outdoor 

unit connecting wire.

Conduct temperature check with outdoor 

controller circuit board after connecting 

‘A-Control Service Tool (PAC-SK52ST)’.

(

)

OCH452B

Содержание PKA-RP100KALR1.TH

Страница 1: ...N OFF TEMP PARTS CATALOG OCB452 INDOOR UNIT PKA RP60KAL TH PKA RP60KAL TH ER PKA RP60KALR1 TH PKA RP60KALR1 TH ER PKA RP71KAL TH PKA RP71KAL TH ER PKA RP71KALR1 TH PKA RP71KALR1 TH ER PKA RP100KAL TH...

Страница 2: ...ZRP60 71VHA PUHZ RP35 50 60 71VHA4 PUHZ RP100 125 140VKA PUHZ RP100 125 140 200 250YKA PU H P71 100VHA PU H P71 100 125 140YHA PUHZ HRP100VHA2 PUHZ HRP100YHA2 PUHZ ZRP100VKA2 UK PUHZ ZRP100YKA2 UK PUH...

Страница 3: ...com pressor Do not use a charging cylinder If a charging cylinder is used the composition of refrigera nt will change and the efficiency will be lowered Flare tool Electronic refrigerant charging scal...

Страница 4: ...rse flow check Attach on vacuum pump 6 Refrigerant charge base 7 Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon 8 Refrigerant recovery equipment 1 Cautions for service 1...

Страница 5: ...isplays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has been...

Страница 6: ...46 kW A kW K min CFM Pa mmAq kW dB mm in mm in mm in mm in kg lb Mode Power supply phase cycle voltage Input Running current External finish Panel Heat exchanger Fan Fan drive o No Fan motor output A...

Страница 7: ...20 230 240V 50Hz 10 0 15 0 20 0 25 0 30 0 35 0 40 0 45 0 50 0 55 0 60 0 65 0 70 0 63 125 250 500 1k 2k 4k 8k NC 60 NC 50 Octave band pressure level dB 0dB 20 Pa Approximate minimum audible limit on co...

Страница 8: ...T STAND BY lamp Receiver Knockout hole for right piping Mount board Right side 444 Gas pipe 482 Liquid pipe 585 Drain hose Filter hook Under side Vane auto Knockout hole for lower piping Louver manual...

Страница 9: ...te controller transmission line TB6 TH2 SW1 TH5 SW2 SWE LEGEND TO OUTDOOR UNIT 5 3 1 3 1 CN01 BLK ORN YLW BLU RED GRN YLW I B w1 Fig 1 I B TB2 POWER SUPPLY 1PHASE 230V 50Hz ORN ORN YLW BRN TB4 INDOOR...

Страница 10: ...low in heating Strainer 50 Strainer 50 Heat exchanger Refrigerant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 8 PKA RP60KAL TH PKA RP71KAL TH PKA RP10...

Страница 11: ...ording to 9 4 TROUBLESHOOTING BY INFERIOR PHENOMENA The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as the work of protection devices in the refrigerant circuit i...

Страница 12: ...s cancelled Procedure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote control...

Страница 13: ...Number of times Wireless remote controller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Dr...

Страница 14: ...sible due to system start up Correct operation Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Inc...

Страница 15: ...heck resistance value of thermistor For characteristics refer to P1 above 2 Check contact failure of connector CN44 on the indoor controller board Refer to 9 7 TEST POINT DIAGRAM Turn the power on and...

Страница 16: ...or fan motor Fan motor is defective Indoor controller board is defec tive 5 Defective outdoor fan control 6 Overcharge of refrigerant 7 Defective refrigerant circuit clogs 8 Bypass circuit of outdoor...

Страница 17: ...Set one of the remote controllers main if there is no problem with the action above 3 Check wiring of remote controller Total wiring length max 500m Do not use cable 3 or more The number of connecting...

Страница 18: ...ler circuit board to transmit signals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board 1 Defective indoor controller board 1...

Страница 19: ...ouble 2 Drain defective Drain pump clogging Drain pipe clogging 3 Open circuit of float switch 4 Contact failure of float switch connector 5 Dew condensation on float switch Drain water descends along...

Страница 20: ...al block S1 and S2 When 220 240 V AC is not detected check indoor outdoor unit connecting wire for miswiring When 220 240 V AC is detected check 4 below 4 Check the fuse on indoor controller board Che...

Страница 21: ...k the connection of remote controller wires in the case of twin triple indoor unit system When 2 or more indoor units are wired in one refrigerant system connect remote controller wires to one of thos...

Страница 22: ...unit operates as follows 1 Indoor fan is running at high speed 2 Drain pump is operating Note on the wireless remote control When the remote control does not function it is possible to activate Emerg...

Страница 23: ...llow 1 Brown Orange 3 Green 5 Connect pin No M Refer to 9 6 2 DC Fan motor fan motor indoor controller circuit board 0 10 20 30 40 50 20 10 0 10 20 30 40 50 Thermistor for lower temperature Temperatur...

Страница 24: ...VDC 310 340 V DC TEST POINT 2 VCC between 4 and 3 of the fan connector VCC 15 V DC Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replac...

Страница 25: ...re J41 J42 Pair No setting for wireless remote controller CN01 Connect to the Terminal block TB4 1 3 220 240 V AC LED1 Power supply I B LED2 Power supply R B LED3 Transmission Indoor outdodr CN3C Tran...

Страница 26: ...The pair number settings of the wireless remote controller and indoor control PCB J41 J42 are given in the table on the left in the table indicates the jumper wire is disco nnected Marks in the table...

Страница 27: ...d Back up function Outline of functions Main and sub unit operate alternately according to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch se...

Страница 28: ...itoring the request code of current setting Setting contents Rotation ON Alternating interval 28days and back up function Rotation ON Alternating interval 14days and back up function Rotation ON Alter...

Страница 29: ...en D when Maintenance monitor is activated The display D now allows you to set a request code No 4 Press the TEMP and buttons 4 to select the desired refrigerant address 5 Press the CLOCK and buttons...

Страница 30: ...tors on the indoor controller board See Photo 3 4 Remove the switch board holder and open the cover 5 Pull out the indoor controller board toward you then remove the indoor controller board and switch...

Страница 31: ...r to 1 2 Remove the electrical box covers Refer to 2 3 Disconnect the vane motor connector CN151 on the indoor controller board 4 Pull out the drain hose from the nozzle assembly and remove nozzle ass...

Страница 32: ...eat exchanger See Photo 9 10 Lift the heat exchanger and pull out the line flow fan to the lower left Photo 7 7 Removing the pipe temperature thermistor liquid TH2 and cond eva temperature thermistor...

Страница 33: ...f the heat exchanger See Photo 9 7 Remove the heat exchanger 9 Removing the room temperature thermistor 1 Remove the panel and corner box Refer to 1 2 Remove the electrical box covers 3 Remove the roo...

Страница 34: ...2009 MITSUBISHI ELECTRIC CORPORATION Distributed in Jul 2014 No OCH452 REVISED EDITION B Distributed in May 2011 No OCH452 REVISED EDITION A Distributed in Feb 2009 No OCH452 PDF 6 Made in Japan New...

Отзывы: