3.3.  Room temperature adjustment

To change room temperature

Press the 

1

 [Set Temperature] Button and set the room temperature of your 

choice.

Pressing 

 or 

 once changes the setting by 1 °C/1 °F .

If the pressing is continued, the setting continues to change by 1 °C [2 °F].

• 

Indoor temperature can be set within the following range.

 

Cooling/dry  :19 °C [67 °F] - 30 °C [87 °F]

 

Heating 

:17 °C [63 °F] - 28 °C [83 °F]

• 

Temperature cannot be set for the fan mode.

The range of room temperature display is 8 °C [46 °F] - 39 °C [102 °F]. Outside 
this range, the display fl ashes either 8 °C [46 °F] - 39 °C [102 °F] to inform you 
if the room temperature is lower or higher than the displayed temperature.

3.4.  Fan speed adjustment

To change fan speed

Every time you press the 

6

 [Fan Speed] button once, it switches from the low-speed 

to high-speed settings successively.

In the electronics dry operation, the indoor fan automatically turns to low-speed 
operation. Switching of fan speed is impossible. (Only the display on the remote 
controller changes.)

Every time the fan speed adjustment button is pressed once, the fan speed is changed.

Fan speed : 3 stages

Display:    (Low)

 

 (Mid)

 

 (High)

 

 (AUTO*)

This setting can be adjusted only with MA remote controller.

3.5. Ventilation

• 

The ventilation unit (OA processing unit or LOSSNAY) automatically goes into 
operation when the indoor unit that is interlocked with it goes into operation.

• If 

the 

8

 [Ventilation] button is pressed while the indoor unit is stopped, only 

the ventilator goes into operation.

• Press 

the 

8

 [Ventilation] button to change the fan speed.

• 

Depending on the models, the indoor unit fan goes into operation while the unit 
is in the ventilation mode.

3.6. Others

 

 

:  Displayed when control is executed by a separately 

sold centralized control unit, etc.

 

STAND BY 
DEFROST

 

:  Displayed from the start of heating operation until the 

moment warm air blows out.

 

CHECK

 

:  This displays indication when some abnormality oc-

curs in the unit.

 

NOT AVAILABLE

 

:  When a Button is pressed for any function which 

the indoor unit cannot perform, this display fl ashes 
concurrently with the display of that function.

 

 

:  In the system in which the [Sensor] display is indi-

cated as the “remote controller”, room temperature 
measurement is performed by the room temperature 
sensor built into the remote controller.

 

FILTER

 

:  Displayed when it is time to clean the fi lter.

   

Press 

the 

A

 [FILTER ( )] Button twice, then the display 

is disappeared.

For fan

Press the 

3

 [Mode (BACK)] Button and bring up the “

FAN

” display.

• 

The fan operation functions to circulate the air in the room.

• 

The temperature of the room cannot be set by fan operation.

 Caution:

Never expose your body directly to cool air for a long time. Excessive expo-
sure to cool air is bad for your health, and should therefore be avoided.

Dry operation

The dry is a microcomputer-controlled dehumidifying operation which controls 
excessive air-cooling according to the room temperature of your choice. (Not us-
able for heating.)

1.  Until reaching room temperature of your choice
 

The compressor and indoor fan function is linked motion according to the 
change of the room temperature and automatically repeat ON/OFF.

2.  When reaching room temperature of your choice
 

Both the compressor and indoor fan stop.

 

When stop continues for 10 minutes, the compressor and indoor fan are oper-
ated for 3 minutes to keep the humidity low.

For heating

Press the 

3

 [Mode (BACK)] Button to bring up the “

HEAT

” display.

Regarding displays during heating operation “DEFROST”

Displayed only during the defrosting operation.

“STAND BY”

Displayed from the start of heating operation until the moment warm air blows out.

 Caution:

• 

When the air-conditioner is used together with burners, thoroughly venti-
late the area. Insuffi cient ventilation can result in accidents due to oxygen 
defi ciency.

• 

Never place a burner at a place where it is exposed to the airfl ow from 
the air-conditioner.

 

Doing so can result in imperfect combustion of the burner.

• 

The microcomputer functions in the following cases: 

• 

Air does not blow out when heating starts. 

-  To prevent any cool air from escaping, the indoor fan is gradually switched in 

sequence from faint airfl ow/weak airfl ow/set airfl ow according to the temperature 
rise of the blown out air. Wait a moment until the airfl ow comes out naturally.

• 

The fan is not moving at the set speed. 

-  In some models, the system switches over to faint airfl ow when the temper-

ature of the room reaches the set temperature. In other cases, it stops to 
prevent any cool air from escaping during the defrosting operation.

• Air 

fl ows out even if operation is stopped.

-  Approximately 1 minute after the stop of operation, the indoor fan sometimes 

rotates to eliminate extra heat generated by the electric heater, etc.

  The fan speed comes to low or high.

4. The smart way to use

Even minimal steps to care for your air conditioner can help make its use far 
more effective in terms of air-conditioning effect, electricity charges, etc.

Set the right room temperature

• 

In cooling operation, a temperature difference of about 5 °C [9 °F] between 
indoors and outdoors is optimum.

• 

If the room temperature is raised by 1 °C [2 °F] during air-cooling operation, 
about 10 % electric power can be saved.

• 

Excessive cooling is bad for health. It also results in the waste of electric power.

Clean the fi lter thoroughly

• 

If the screen of the air fi lter becomes clogged, the airfl ow and air-conditioning 
effect can be signifi cantly reduced.

 

Further, if the condition is left unattended, failure can result. It is particularly 
important to clean the fi lter at the beginning of the cooling and heating seasons. 
(When profuse dust and dirt have accumulated, clean the fi lter thoroughly.)

Prevent intrusion of heat during air-cooling

• 

To prevent the intrusion of heat during cooling operation, provide a curtain or a 
blind on the window to block out direct sunlight. Also, do not open the entrance 
or exit except in cases of dire necessity. 

Carry out ventilation sometimes

• 

Since the air periodically gets dirty in a room that is kept closed for a long time, 
ventilation is sometimes necessary. When gas appliances are used together 
with the air conditioner, special precautions must be taken. If the “LOSSNAY” 
ventilation unit developed by our company is used, you can perform ventilation 
with less waste. For details on this unit, consult with your dealer.

WT06599X01.indb   7

WT06599X01.indb   7

3/23/2012   5:22:06 PM

3/23/2012   5:22:06 PM

Содержание PEFY-P06NMAU-E2

Страница 1: ...F OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit MANUEL D UTILISATION Pour une utilisation correcte sans risques veuil...

Страница 2: ...OFF FILTER CHECK CLEAR MENU ON OFF TEST TEMP CLOCK OPERATION BACK DAY MONITOR SET 1 2 3 4 D 5 6 8 9 C 0 A B 7 Remote controller Button Touche Commande distance GB F 1 Touche R glage de la temp rature...

Страница 3: ...i ce N R glage des ailettes O Vitesse du ventilateur P T moin de fonctionnement Remote controller Display Affichage Commande distance GB F A Current time Timer time B Centralized control indicator C T...

Страница 4: ...4 4 2 In case of bottom inlet En cas d entr e sur le dessous 1 In case of rear inlet En cas d entr e arri re A Filter Filtre Air Flow Flux d air A 1 A 2 Fig A...

Страница 5: ...se of the wrong type of refrigerant 1 Outdoor unit Warning The outdoor unit must be installed on a stable level surface in a place where there is no accumulation of snow leaves or rubbish Do not stand...

Страница 6: ...t consult your dealer If pipes are removed incorrectly refrigerant fluorocarbon gas may blow out and come into contact with your skin causing injury Releasing refrigerant into the atmosphere also dama...

Страница 7: ...n according to the change of the room temperature and automatically repeat ON OFF 2 When reaching room temperature of your choice Both the compressor and indoor fan stop When stop continues for 10 min...

Страница 8: ...Heating operation starts after ending defrosting operation It runs briefly but soon stops The CHECK and check code flashes on the liquid crystal display There are some obstacles at the air inlet and o...

Страница 9: ...the professional engineering work required for transferring the instal lation Caution When moving or reinstalling the air conditioner consult with your dealer Defective installation can result in ele...

Страница 10: ...he operating noise is the data that was obtained in an anechoic room Item Model P36NMAU E2 P48NMAU E2 P54NMAU E2 Power source 208 230V 60Hz Cooling capacity 1 Heating capacity 1 Btu h 36 000 40 000 48...

Страница 11: ...e r frig rant 1 Appareil ext rieur Avertissement L appareil ext rieur doit tre install sur une surface plane et stable dans un endroit non sujet l accumulation de neige de feuilles ou de d tritus Ne p...

Страница 12: ...ment Lorsque vous devez ranger l appareil veuillez consulter votre revendeur Si les tuyaux ne sont pas correctement retir s du produit r frig rant gaz fluorocarbonique pourrait s chapper et entrer en...

Страница 13: ...arr t ON OFF 2 Lorsque la temp rature de votre choix est atteinte le compresseur et le ven tilateur int rieur s arr tent tous deux Si l arr t dure plus de 10 minutes le compresseur et le ventilateur i...

Страница 14: ...in e Le climatiseur fonctionne pendant un bref instant puis s arr te aussit t Le code et la mention de v rification CONTROLE clignotent sur l affichage cristaux liquides Des obstacles bloquent l arriv...

Страница 15: ...lez prendre contact au pr alable avec le revendeur pour une estimation du co t des travaux requis pour le d m na gement de l installation Pr caution Lors du d m nagement et de la r installation du cli...

Страница 16: ...d usine 3 Le bruit entendu durant le fonctionnement est d aux informations obtenues dans une chambre sourde El ment Mod le P36NMAU E2 P48NMAU E2 P54NMAU E2 Alimentation 208 230V 60Hz Capacit de refroi...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...ss telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE TOKYO BLDG...

Отзывы: