74
CHAPTER 8
FUNCTION
This chapter describes the details of the functions available in the D/A converter module, and the setting procedures
for those functions.
For details on remote I/O signals, remote registers, and remote buffer memory, refer to the following.
• Details of Remote I/O Signals (
• Details of Remote Register Areas (
• Details of Remote Buffer Memory Areas (
8.1
D/A Conversion Enable/Disable Function
Sets whether to enable or disable D/A conversion for each channel.
Disabling the D/A conversion for unused channels reduces the conversion cycles.
(1) Setting procedure
1.
Set "Parameter write" for "Method selection".
"CC IE Field Configuration" window
Select a D/A converter module in "List of stations"
[CC IE Field Configuration]
[Parameter Processing of Slave Station]
2.
Set "CH
D/A conversion enable/disable setting" to "0: Enable".
8.2
D/A Output Enable/Disable Function
Whether to output the D/A conversion value or the offset value can be set for each channel.
The conversion speed is constant, regardless of the output enable/disable status.
(1) Setting procedure
Use CH
Output enable/disable flag (RY10 to RY13) for the setting.
CH
Output enable/disable flag (RY10 to RY13)
Analog output
Output enable (ON)
The D/A conversion value is output.
Output disable (OFF)
The offset value is output.