280
PID control
Pre-charge operation at output shutoff
When the pre-charge operation is valid, the pre-charge operation is performed at the output shutoff cancellation.
(The pre-charge operation is also performed even if the automatic restart after instantaneous power failure is valid.)
When the operation method is changed to PID control from another control
When the control method is changed to PID control from a control with higher priority in frequency command (multi-
speed setting, Jog operation, etc.), the motor is accelerated/decelerated until its speed reaches the automatic
switchover frequency, and the pre-charge is performed.
When the output is shutoff during PID control, which is performed after the pre-charge operation
When the output is shutoff during the pre-charge operation
REMARKS
If the output shutoff is canceled while the X77 signal is ON, the pre-charge operation is not performed and PID control is
performed.
STF
MRS
X77
OFF
Y49
Pre-charge
Pre-charge
Y47
Output signal
PID control
PID control
Pr.127
0Hz
Pr.762
Pr.762
Output frequency[Hz]
Output
shutoff
Pre-charges again.
Time
Pr.127
0Hz
STF
MRS
Pr.762
Pr.762
Y47
Output signal
PID control
Y49
Pre-charge
Pre-charge
Output frequency[Hz]
Pre-charge
Output shutoff
Time
Pr.127
0Hz
STF
Pr.762
Y49
Pre-charge
Multi-speed operation
RH
Y47
Output signal
PID control
Time