Frequency setting by analog input (terminal 1, 2, 4)
4.16.5 4mA input check of current input (Pr. 573, Pr. 777, Pr. 778)
The above parameters can be set when
Pr. 160 User group read selection
= "0".
(Refer to page 192.)
....
Specifications differ according to the date assembled.
to check the SERIAL number.
When inputting 4 to 20mA current to terminal 2 or terminal 4, decrease in analog current input is detected to
enable continuous operation even if input has decreased.
Parameter
Number
Name
Initial Value
Setting
Range
Description
573
4mA input check
selection
9999
1
When the current input drops to or below 2mA, the LF
signal is output and inverter continues operation at the
frequency (average value) just before current reaches 2mA.
2
When the analog input current drops to or below 2mA, the
fault (E.LCI) is output and the inverter output is shutoff.
3
When the analog input current drops to or below 2mA, the
alarm signal (LF) is output, and the fault (E.LCI) is output
after deceleration to a stop. When the current rises to or
above 3mA during the deceleration, the motor accelerates
again to the set point and resumes normal operation.
4
When the analog input current drops to or below 2mA, the
alarm signal (LF) is output and the inverter continues
operation at the
Pr. 777
setting.
9999
4mA input is not checked.
777
4mA input fault
operation
frequency
9999
0 to 400Hz
Set the frequency to continue the operation when the
analog input current drops to or below 2mA while
Pr. 573
="4."
9999
4mA input is not checked while
Pr. 573
= "4."
778
Current input check
filter
0
0 to 10s
Detection for an analog input current drop is performed for
the time period of
Pr. 778
while the analog input current
≤
2mA.
Detection for an analog input current drop is cancelled for
the time period of
Pr. 778
while the analog input current >
3mA.
Pr. 778
=0: Immediately detected or the detection is
cancelled.
* When
Pr.573
= "1", input decrease is detected (LF signal output) even if
the analog input value to bias frequency of terminal 2 or terminal 4 is set
to 2mA or less using
C2 (Pr. 902)
or
C5 (Pr. 904)
and the value is not as
bias frequency settings.
(1) Operation continuation (
Pr. 573
= "1")
⋅
When the input current of terminal 4 (terminal 2) falls 2mA
or below, output alarm output signal (LF) is output.
⋅
When the current falls below 2mA, the output frequency
(average value) before detection is retained and operation
at the retained frequency continues.
⋅
When the current input increases above 3mA, the LF
signal output is turned OFF and the inverter operates
according to the current input.
⋅
For the LF signal, set "98 (positive logic) or 198 (negative
logic)" in
Pr. 190 to Pr. 196 (output terminal function selection)
and assign functions to the output terminal.
⋅
Since turning OFF the start command clears the
retained frequency, the inverter does not operate at the
retained frequency even if restarted.
4mA
2mA
60Hz
20mA
Set frequency
Analog input
When C3(C6) = 0%
Normal use range
Current input
decrease detection
*