TECHNICAL CHANGES
INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT
• This room air conditioner adopts HFC refrigerant (R410A) which never destroys the ozone layer.
• Pay particular attention to the following points, though the basic installation procedure is same as that for R22 air
conditioners.
1
As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/
materials are required. Refer to the table below.
2
Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and
installation, since it is more susceptible to contaminations than R22.
3
For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant
piping.)
4
Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent
composition change.
MUZ09UN
➔
MUZ-A09NA
MUZ12UN
➔
MUZ-A12NA
MUH15TN
➔
MUZ-A15NA
MUH17TN
➔
MUZ-A17NA
MUH24WN
➔
MUZ-A24NA
MU15TN
➔
MUY-A15NA
MU17TN
➔
MUY-A17NA
MU24WN
➔
MUY-A24NA
1. Outdoor unit model has been changed.
2. Control method between indoor and outdoor unit has been changed.
3. Refrigerant has been changed. (R22
➔
R410A)
4. Fan motor has been changed. (AC
➔
DC)
5. Compressor has been changed. (AC
➔
DC)
Refrigeration
oil
Refrigerant
New refrigerant
R410A
HFC-32: HFC-125 (50%:50%)
Pseudo-azeotropic refrigerant
Not included
A1/A1
72.6
-60.5
225.82
3.995
Non combustible
0
1730
From liquid phase in cylinder
Possible
Incompatible oil
Non
Non
Previous refrigerant
R22
R22 (100%)
Single refrigerant
Included
A1
86.5
-41.4
136.34
2.772
Non combustible
0.055
1700
Gas phase
Possible
Compatible oil
Light yellow
Non
Refrigerant
Composition (Ratio)
Refrigerant handling
Chlorine
Safety group (ASHRAE)
Molecular weight
Boiling point (
°
F)
Steam pressure [77
°
F](PSIG)
Saturated steam density [77
°
F](lb/ft
3
)
Combustibility
ODP
w
1
GWP
w
2
Refrigerant charge method
Additional charge on leakage
Kind
Color
Smell
w
1 :Ozone Destruction Parameter : based on CFC-11
w
2 :Global Warmth Parameter
: based on CO
2
OB451--1.qxp 06.3.29 9:51 AM Page 2
Содержание MUY-A15NA
Страница 11: ...11 WIRING DIAGRAM 5 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA...
Страница 12: ...12 MUY A15NA MUY A17NA...
Страница 13: ...13 MUZ A24NA...
Страница 14: ...14 MUY A24NA...
Страница 68: ...68 2 OUTDOOR UNIT ELECTRICAL PARTS 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 3 5 6 7...
Страница 74: ...74 2 OUTDOOR UNIT ELECTRICAL PARTS 8 1 4 MUZ A09NA MUZ A12NA MUZ A15NA MUZ A17NA MUY A15NA MUY A17NA 2 3 5 6 7...