9
Outdoor unit
precharged
850g
Refrigerant piping length (one way)
Unit B + Unit C
Outdoor unit
precharged
850g
Refrigerant piping length (one way, 2 unit total)
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Max.
limits
UNIT No.
Unit A
Unit B
Unit C
Pipe length
15m
15m
Total
30m
L
B
+
L
C
15m
L
A
L
B
L
C
Height difference (H)
10m
10m
10m
No. of bends
10
10
Total
15
10
PIPING PREPARATION
1
Table below shows the specifications of pipes commercially available.
2
Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
3
Refrigerant bending radius must be 100mm or more.
Unit A
7m
0
8m
20
9m
40
10m
60
11m
80
12m
100
13m
120
14m
140
15m
160
10
m
11
m
12
m
13
m
14
m
15
m
16
m
17
m
18
m
19
m
20
m
21
m
22
m
23
m
24
m
25
m
26
m
27
m
28
m
29
m
30
m
0
10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160 170 180 190 200
UNIT No.
Insulation
thickness
Pipe
For liquid
For gas
For liquid
For gas
Outside diameter
mm
6.35
12.7
6.35
9.52
8mm
8mm
8mm
8mm
Insulation material
Heat resisting foam plastic
0.045 specific gravity
Unit A
Unit B and Unit C
9
The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions,
since operating conditions vary according to the areas where these units are installed. The following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198~264V, 50Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS
(1) Indoor intake air wet-bulb temperature :
°CWB
(2) Indoor outlet air wet-bulb temperature :
°CWB
(3) Outdoor intake air dry-bulb temperature :
°CDB
(4) Total input:
W
Indoor air wet/dry-bulb temperature difference on the left side of the chart on page 10 shows the difference between the
indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.
PERFORMANCE CURVES
MUX-A22WV -
E1