21
Start
Indoor unit
operates.
Outdoor unit
doesn't
operate.
Indoor unit
doesn't receive
the signal from
remote controller.
Indoor unit
operates.
Outdoor unit
doesn't operate
normally.
OPERATION INDICATOR
lamp on the indoor unit is
flashing on and off.
Outdoor unit
operates in
only Test Run
operation.
Outdoor unit
doesn't
operate
even in
Test Run
operation.
Indoor unit
operates, when
the EMERGENCY
OPERATION
switch is pressed.
Indoor unit
doesn't operate,
when the
EMERGENCY
OPERATION
switch is pressed.
Check room
temperature
thermistor.
Refer to
"Test point
diagram and
voltage" on
page 27.
Refer to
"Check of
outdoor unit".
Refer to
B
"Check of
remote controller
and receiver
P.C. board"
on page 24.
Flash on and
off at 0.5-
second
intervals
Cause:
Indoor/
Outdoor unit
• Mis-wiring
2-time flash
Cause:
Indoor unit
• Trouble of
room temp-
erature/
indoor coil
thermistor
3-time flash
Cause:
Indoor unit
• Trouble of
indoor fan
motor
6-time flash
Cause:
Outdoor unit
• Trouble of
thermistor
in outdoor
unit
7-time flash
Cause:
Outdoor unit
• Trouble of
outdoor
control
system
Refer to
D
"How to
check
mis-wiring
(When
outdoor unit
doesn't work)"
on page 26.
Check room
temperature
thermistor
and indoor
coil thermis-
tor.
Refer to
"Test point
diagram and
voltage"
on page 27.
Refer to
A
"Check of
indoor fan
motor"
on page 24.
Refer to
"Check of
outdoor
thermistor".
MUH type
Replace the
deicer
P.C. board.
MXZ type
Replace the
outdoor
electronic
control
P.C. board.
10-time flash
Cause:
Outdoor unit
MUH-A30WV
• Trouble of
low discharge
temperature
protection
MXZ type
• Outdoor
refrigerant
system
abnormality
MUH-A30WV
Refer to
"Check of
LEV".
MXZ type
Refer to
outdoor
refrigerant
system
related items.
4-time flash
Cause:
Indoor unit
• Trouble of
indoor unit
control
system
Replace the
indoor
electronic
control
P.C. board.
As for outdoor unit MUH type, refer to service manual OB322.
1. Check indoor /
outdoor
connecting wire.
2. Refer to
C
"Check of indoor
electronic control
P.C. board"
on page 25.
Outdoor unit
doesn't
stop even
if indoor unit
stops.
Unit doesn't
operate
normal
operation in
COOL or
HEAT mode.
Refer to
"Check of
outdoor unit".
Refer to
"Check of
R.V. coil".
As for outdoor unit MXZ type, refer to service manual OB319.
MXZ type
5-time flash
Cause:
Outdoor unit
• Outdoor
power
system
abnormality
Refer to
"Check of
inverter/
compressor"
and "Check
of power
supply".
10-2. Instruction of troubleshooting
OB321-1.qxp 03.11.13 4:03 PM Page 21