background image

27

Check code Abnormal point and detection method 

Cause

Countermeasure

P6

Freezing/overheating protection is 

operating

 Freezing protection (Cooling mode)

The unit is in 6-minute resume 

prevention mode if pipe <liquid or 

condenser/evaporator> temperature 

stays under −15˚C for 3 minutes, 3 

minutes after the compressor started. 

Abnormal if it stays under −15˚C for 3 

minutes again within 16 minutes after 

6-minute resume prevention mode.

 Overheating protection (Heating mode)

The unit is in 6-minute resume 

prevention mode if pipe <liquid or 

condenser/evaporator> temperature 

is detected as over 70˚C after the 

compressor started. Abnormal if the 

temperature of over 70˚C is detected 

again within 30 minutes after 6-minute 

resume prevention mode.

P8

 Slight temperature difference 

  

between indoor room 

temperature and pipe <liquid 

or condenser/evaporator> 

temperature thermistor

• Shortage of refrigerant

• Disconnected holder of 

pipe <liquid or condenser/ 

evaporator> thermistor

• Defective refrigerant circuit

 Converse connection of 

extension pipe (on plural units 

connection)

 Converse wiring of indoor/

outdoor unit connecting wire 

(on plural units connection)

 Defective detection of indoor 

room temperature and pipe 

<condenser/evaporator> 

temperature thermistor

 Stop valve is not opened 

completely.

(Cooling or drying mode)

 Clogged filter (reduced airflow)

 Short cycle of air path

 Low-load (low temperature) 

operation out of the tolerance 

range

 Defective indoor fan motor

 • Fan motor is defective.

 • Indoor controller board is defec-

tive.

 Defective outdoor fan control

 Overcharge of refrigerant

Defective refrigerant circuit 

(clogs)

(Heating mode)

 Clogged filter (reduced airflow)

 Short cycle of air path

 Over-load (high temperature) 

operation out of the tolerance 

range

 Defective indoor fan motor

 • Fan motor is defective.

 • Indoor controller board is defec-

tive.

 Defective outdoor fan control

 Overcharge of refrigerant

 Defective refrigerant circuit 

(clogs)

 Bypass circuit of outdoor unit 

is defective. 

(Cooling or drying mode)

 Check clogs of the filter.

 Remove blockage.

 Refer to "10-6. HOW TO CHECK THE 

PARTS". 

 Check outdoor fan motor. 

  Check operating condition of refrigerant 

circuit.

(Heating mode)

 Check clogs of the filter.

 Remove blockage.

 Refer to "10-6. HOW TO CHECK THE 

PARTS". 

 Check outdoor fan motor. 

Check operating condition of refrigerant 

circuit.

Pipe temperature

<Cooling mode>

Detected as abnormal when the pipe 

temperature is not in the cooling range 

3 minutes after compressor start and 6 

minutes after the liquid or condenser/

evaporator pipe is out of cooling range.

Note 1: It takes at least 9 minutes to detect.

Note 2: Abnormality P8 is not detected in 

drying mode.

Cooling range : −3°C   (TH−TH1) 

TH: Lower temperature between liquid pipe 

temperature (TH2) and condenser/

evaporator temperature (TH5)

TH1: Intake temperature 

<Heating mode>

When 10 seconds have passed after the 

compressor starts operation and the hot 

adjustment mode has finished, the unit is 

detected as abnormal when condenser/

evaporator pipe temperature is not in 

heating range within 20 minutes. 

Note 3: It takes at least 27 minutes to 

detect abnormality.

Note 4: It excludes the period of defrosting. 

(Detection restarts when defrosting 

mode is over.)

Heating range: 3°C 

 

(TH5−TH1)  

 

Check pipe <liquid or condenser/evapo-

rator> temperature with room tempera-

ture display on remote controller and 

outdoor controller circuit board.

 

Pipe <liquid or condenser/evaporator> 

temperature display is indicated by set-

ting SW2 of outdoor controller circuit 

board as follows.

Check converse connection of extension 

pipe or converse wiring of indoor/outdoor 

unit connecting wire.

Conduct temperature check with outdoor 

controller circuit board after connecting 

‘A-Control Service Tool(PAC-SK52ST)’.

(

)

OCH491D

Содержание Mr.Slim PCA-RP100KAQ

Страница 1: ...Revision Added PCA RP35KAQR2 PCA RP35KAQR2 ER PCA RP50KAQR2 PCA RP50KAQR2 ER PCA RP60KAQR2 PCA RP60KAQR2 ER PCA RP71KAQR2 PCA RP71KAQR2 ER PCA RP100KAQR2 PCA RP100KAQR2 ER PCA RP125KAQR2 PCA RP125KAQ...

Страница 2: ...PCA RP71KAQR2 ER PCA RP100KAQ PCA RP100KAQR2 ER PCA RP125KAQ PCA RP125KAQR2 ER PCA RP140KAQ PCA RP140KAQR2 ER S W for dual set temperature has been changed PCA RP50KAQ PCA RP50KAQR1 PCA RP60KAQ PCA RP...

Страница 3: ...40YHAR3 UK OC379 PUHZ P100 125 140VHA3 PUHZ P100 125 140YHA PUHZ P100VHA4 PUHZ P100YHA2 PUHZ P100 125 140VHA3R2 UK PUHZ P100 125 140YHAR1 UK PUHZ P100VHA4 UK PUHZ P100YKA2R1 UK OCH415 OCB415 PUHZ P200...

Страница 4: ...ing tools specifically designed for use with R410A refrigerant The following tools are necessary to use R410A refrigerant Handle tools with care If dirt dust or moisture enters into refrigerant cycle...

Страница 5: ...eck Attach on vacuum pump Refrigerant charge base Refrigerant cylinder Only for R410A Top of cylinder Pink Cylinder with syphon Refrigerant recovery equipment 1 Cautions for service 1 Perform service...

Страница 6: ...splays whether timer is on or off Buttons used to set the hour and minute of the current time and timer settings h and min buttons display display FAN SPEED display indicates which fan speed has been...

Страница 7: ...he Installation Manual All icons are displayed for explanation 5 6 1 2 3 4 Press to turn ON OFF the indoor unit 1 ON OFF button This lamp lights up in green while the unit is in operation It blinks wh...

Страница 8: ...be displayed Maintenance Auto descending panel Auto descending panel Optional parts Up Down you can do Manual vane angle Use to set the vane angle for each vane to a fixed position Initial setting Ma...

Страница 9: ...39 C or more Louver display Indicates the action of the swing louver Does not appear if the louver is not running Power On indicator Indicates that the power is on Fan Speed indicator Shows the select...

Страница 10: ...1 16 25 55 PCA RP50KAQ PCA RP50KAQR1 PCA RP50KAQR2 PCA RP50KAQR2 ER kW A kW K min CFM Pa mmAq dB mm in mm in mm in mm in kg lb Service Ref Mode Power supply phase cycle voltage Input Running current...

Страница 11: ...6 PCA RP125KAQ PCA RP125KAQR2 PCA RP125KAQR2 ER kW A kW K min CFM Pa mmAq dB mm in mm in mm in mm in kg lb Service Ref Mode Power supply phase cycle voltage Input Running current External finish Heat...

Страница 12: ...0 14 0 90 PCA RP140KAQ PCA RP140KAQR2 PCA RP140KAQR2 ER kW A kW K min CFM Pa mmAq dB mm in mm in mm in mm in kg lb Service Ref Mode Power supply phase cycle voltage Input Running current External fini...

Страница 13: ...5 2 FRESH AIR INTAKE AMOUNT STATIC PRESSURE CHARACTERISTICS Q 0 B A C 1 Curve in the graphs Duct characteristics at site Q A E C 2 Q Qa A D 3 Q Designed amount of fresh air intake m3 min A Static pres...

Страница 14: ...RESSURE LEVEL dB 0 dB 0 0002 bar BAND CENTER FREQUENCIES Hz PCA RP60KAQ PCA RP60KAQR1 PCA RP60KAQR2 PCA RP60KAQR2 ER 90 80 70 60 50 40 30 20 10 63 125 250 500 1000 2000 4000 8000 APPROXIMATE THRESHOLD...

Страница 15: ...2000 4000 8000 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE NC 60 NC 50 NC 40 NC 30 NC 20 NC 70 BAND CENTER FREQUENCIES Hz OCTAVE BAND SOUND PRESSURE LEVEL dB 0 dB 0 0002 bar PCA RP140KAQ PC...

Страница 16: ...in piping arrangement Refrigerant pipe connection gas pipe side flared connection Refrigerant pipe connection liquid pipe side flared connection 1 In case of the rear pipe arrangement make sure to rem...

Страница 17: ...re when installing the drain pump option parts refrigerant pipe will be only upward Air outlet 233 Electrical box When electrical box is pulled down Electrical box 9 7 In case of the rear pipe arrange...

Страница 18: ...iquid pipe side flared connection 5 1 2 3 4 Ceiling FRONT VIEW Electrical box When electrical box is pulled down 2 NOTES 1 Use M10 or W3 8 screw for anchor bolt 2 Please be sure when installing the dr...

Страница 19: ...19 WIRED REMOTE CONTROLLER Unit mm PAR 21MAA PAR 30MAA PAR 31MAA 130 120 83 5 19 5 19 120 120 46 46 83 5 Option OCH491D...

Страница 20: ...RTS 1 3 REMOCON CN22 BLU WIRELESS CN90 WHT VANE CNV WHT Pair No FAN CNMF WHT INTAKE CN20 RED FLOAT SW CN4F WHT LIQUID PIPE CN44 WHT CN32 WHT CN51 WHT CN41 WHT X1 FUSE 2 R B TB5 TRANSMISSION WIRES DC12...

Страница 21: ...rant GAS pipe connection Flare Refrigerant LIQUID pipe connection Flare REFRIGERANT SYSTEM DIAGRAM 9 PCA RP35KAQ PCA RP50KAQ PCA RP60KAQ PCA RP71KAQ PCA RP35KAQR2 PCA RP50KAQR1 PCA RP60KAQR1 PCA RP71K...

Страница 22: ...rouble according to 10 4 TROUBLESHOOTING OF PROBLEMS The trouble is not reoccurring Logged Not logged 1Consider the temporary defects such as the work of protection devices in the refrigerant circuit...

Страница 23: ...dure 1 Press the CHECK button twice 2 Press the temperature buttons 3 Point the remote controller at the sensor on the indoor unit and press the HOUR button 4 Point the remote controller at the sensor...

Страница 24: ...roller Wired remote controller 1 P1 Intake sensor error P9 Pipe TH5 sensor error 2 P2 Pipe TH2 sensor error 3 E6 E7 Indoor outdoor unit communication error 4 P4 Drain sensor error Float switch connect...

Страница 25: ...ot connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Incorrect wiring between indoor and outdoor units incorrect polarity of S1 S2 S3 Remote controller wire s...

Страница 26: ...oller board Check resistance value of thermistor For characteristics refer to P1 above Check contact failure of connector CN44 on the indoor controller board Refer to 10 7 TEST POINT DIAGRAM Turn the...

Страница 27: ...oor fan motor Fan motor is defective Indoor controller board is defec tive Defective outdoor fan control Overcharge of refrigerant Defective refrigerant circuit clogs Bypass circuit of outdoor unit is...

Страница 28: ...number of connecting remote control ler max 2 units When it is not the above mentioned problem of Diagnose remote controllers a When RC OK is displayed Remote controllers have no problem Turn the pow...

Страница 29: ...nals Indoor controller board Abnormal if data cannot be read normally from the nonvolatile memory of the indoor controller board Defective indoor controller board Replace indoor controller board The c...

Страница 30: ...sconnection of or leakage in refrigerant pipes Air into refrigerant piping Abnormal operation no rotation of indoor fan Defective fan motor Defective indoor control board Defective refrigerant circuit...

Страница 31: ...k S1 and S2 When 220 240 V AC is not detected check indoor outdoor unit connecting wire for miswiring When 220 240 V AC is detected check below Check the fuse on indoor controller board Check the wiri...

Страница 32: ...e connection of remote controller wires in the case of twin triple indoor unit system When 2 or more indoor units are wired in one refrigerant system connect remote controller wires to one of those un...

Страница 33: ...t function it is possible to activate emergency operation by using the indoor unit emergency operation switch SW1 SW2 of the wireless signal receiver board However if the indoor unit microprocessor ha...

Страница 34: ...or short Red Yellow Red Blue Red Orange Red White Connector Normal 300 2 1 Moving part 4 3 Switch Magnet Moving part Yellow Blue Red Orange White MV Refer to 10 6 1 Thermistor 0 10 20 30 40 50 20 10 0...

Страница 35: ...VDC 310 340 V DC TEST POINT 2 VCC between 5 and 4 of the fan connector VCC 15 V DC Wiring recovery Replace the indoor controller board Replace the fan motor Replace the indoor controller board Replac...

Страница 36: ...USE 6 3 A 250 V CNMF Fan motor 1 4 310 340 V DC 5 4 15 V DC 6 4 0 6 5 V DC 7 4 Stop 0 or 15 V DC Operation 7 5 V DC 0 15 V pulse VSP Voltage between pins of C626 0 V DC FAN stop 1 6 5 V DC FAN operati...

Страница 37: ...because these models have the cond eva temperature thermistor TH5 Marks in the table below Jumper wire Short Open Without TH5 With TH5 Model JP1 For product Service parts Indoor controller board type...

Страница 38: ...ion Outline of functions Main and sub unit operate alternately according to the interval of rotation setting Main and sub unit should be set by refrigerant address Outdoor DIP switch setting Refrigera...

Страница 39: ...OFF Monitoring the request code of current setting Setting contents Rotation ON Alternating interval 28days and back up function Rotation ON Alternating interval 14days and back up function Rotation...

Страница 40: ...button and press the button Set the Refrigerant address and Request code Select the item to be changed with the F1 or F2 button Select the required setting with the F3 or F4 button Select the required...

Страница 41: ...tton Select the required setting with the F3 or F4 button Press the F3 or F4 button to set the Refrigerant address 0 Press the F3 or F4 button to set the desired request code No Rotation Back up opera...

Страница 42: ...e terminal blocks and pull out the electrical box See Photo 2 Removing the indoor controller board 6 Remove the 6 supports from the indoor controller board and remove the indoor controller board See P...

Страница 43: ...ver and remove the electrical cover 4 Remove 2 screws from the electrical box and pull the electrical box downward 5 Temporarily secure the electrical box using 2 hooks in the back of electrical box 6...

Страница 44: ...e 4 screws from the fan guard of the fan motor See Photo 5 6 Remove 2 screws from the left side beam and remove the beam See Photo 1 7 Remove the 3 screws from center fan guard and remove the fan guar...

Страница 45: ...ight side panel See Figure 3 4 3 Remove the connector of vane motor 4 Remove 2 screws of vane motor cover then remove vane motor Photo 13 Screws Connector Vane motor and cover Photo 14 Under panel fix...

Страница 46: ...the pipe temperature thermistors liquid TH2 and condenser evaporator temperature themistor TH5 1 Remove the air intake grille See Figure 1 2 2 Remove the left and right side panels See Figure 3 4 3 Re...

Страница 47: ...els See Figure 3 6 Remove the under panel See Photo 14 7 Remove the drain pan See Photo 15 16 17 8 Remove the pipe cover See Photo 18 9 Remove the pipe thermistors TH2 and TH5 from each holder See Pho...

Страница 48: ...1 REVISED EDITION C Distributed in Oct 2012 No OCH491 REVISED EDITION B Distributed in Feb 2012 No OCH491 REVISED EDITION A Distributed in Dec 2010 No OCH491 Made in Japan HEAD OFFICE TOKYO BLDG 2 7 3...

Отзывы: