(2) A1SJ72QLR25, A1SJ72QBR15 

Specifications 

Item 

A1SJ72QLR25 A1SJ72QBR15 

X/Y 8192 

points 

B 8192 

points 

Maximum link 
points per 
network 

W 8192 

points 

Maximum link points per 
station 

y

 Remote master station   remote I/O station                        

   

Y+B

8

+ (2   W)   <1600 bytes     

y

 Remote I/O station   remote master station 

   

X

+B

8

+ (2   W)   <1600 bytes     

y

 Remote master station   remote sub-master station 

Remote sub-master station   remote master station 

   

Y+B

8

+ (2   W)

  

<2000 bytes

     

Maximum number of I/O 
points per remote I/O station 

X+Y<1024 (main base unit + 1 extension base units) 
When X and Y overlap, either of them becomes effective. 

Communication speed 

10Mbps (equivalent to 20Mbps 
for multiple transmission) 

10Mbps 

Communication method 

Token ring 

Token bus  

Synchronization method 

Frame synchronization  

Encoding method 

Manchester encoding 

Transmission route format 

Duplex coaxial loop 

Single coaxial bus 

Transmission format 

Conform to HDLC (frame format) 

Maximum number of networks  239  

65 stations 

33 stations 

Number of stations for 
connection per network 

Remote master station: 1  
Remote I/O stations: 64 

 

Remote master station: 1 
Remote I/O stations: 32 

 

3C-2V 19.2km(300m) 

3C-2V 

300m(300m) 

5C-2V 30km(500m) 5C-2V 

500m(500m) 

Overall distance  
(Station-to-station distance) 
*1 

Can be extended to 2.5km when 
used with a repeater module 
(A6BR10, A6BR10-DC) 

Error control method 

Retry by CRC (X

16

+X

12

+X

5

+1) and overtime 

RAS function 

y

 Loop back function due to abnormality detection and cable 

disconnection (A1SJ72QLR25) 

y

 Diagnostic function for local link circuit check 

y

 Abnormality detection by link special relay, resistor 

y

 Network monitor, each type of diagnostic function 

Transient transmission 

Monitoring with peripheral device, program up/download 

Connection cable 

Equivalent to 3C-2V, 5C-2V cables (Arranged by user) 

Applicable connector 

Equivalent BNC-P-3-NiCAu (For 3C-2V),  
BNC-P-5-NiCAu (For 5C-2V) (DDK) (Arranged by user) 

5VDC current consumption 

1.24A 

0.70A 

Weight 0.42kg 

0.43kg 

*1: The distance between stations is restricted in accordance with the type of cable and number 

of stations. Refer to Reference Manual of master module in use for details. 

For general specifications of the network module, refer to the user's manual for the PLC CPU 
that is to be used. 
 

 

 

Содержание MELSECNET/10 A1SJ72QLP25

Страница 1: ...uying the Mitsubishi general purpose programmable logic controller MELSEC QnA Series Prior to use please read both this manual and detailed manual thoroughly and familiarize yourself with the product MODEL A1SQ NET10 R U JE MODEL CODE 13JQ94 IB NA 0800111 B 0605 MEE 2000 MITSUBISHI ELECTRIC CORPORATION ...

Страница 2: ... required Always forward it to the end user INSTALLATION PRECAUTIONS CAUTION z Use the PLC in an environment that meets the general specificaitons contained in CPU module user s manual Using this PLC in an environment outside the range of the general specifications could result in electric shock fire erroneous operation and damage to or deterioration of the product z Fully insert the projection on...

Страница 3: ... may cause a malfunction z Be sure there are no foreign substances such as sawdust or wiring debris inside the module Such debris could cause fires damage or erroneous operation z Make sure to place the communication and power cables into a duct or fasten them using a clamp Cables not placed in the duct or not clamped may hang or shift allowing them to be accidentally pulled which may cause a modu...

Страница 4: ...e with the EMC Directive and the Low Voltage Directive Chapter 1 2 3 4 5 6 This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi electric Corporation cannot be held responsible for any problems involving industrial property rights which may occur as a result of using the contents noted in this manual 2000 MITSUBISHI ELEC...

Страница 5: ...1 2 Performance Specifications 2 3 Handling 4 3 1 Cable length restrictions between stations 4 4 The Name and Setting of Each Part 5 5 Wiring 9 6 External Dimensions 10 6 1 A1SJ72QLP25 10 6 2 A1SJ72QLR25 10 6 3 A1SJ72QBR15 11 ...

Страница 6: ...e and the Low Voltage Directive When incorporating the Mitsubishi PLC into other industrial machinery or equipment and keeping compliance with the EMC and low voltage directives refer to Chapter 3 EMC Directive and Low Voltage Instruction of the User s Manual Hardware for the CPU module used or the PLC CPU supplied with the base unit The CE logo is printed on the rating plate of the PLC indicating...

Страница 7: ...1SJ72QBR15 For remote I O station of MELSECNET 10 Main base CPU slot 2 After unpacking the Network Modules confirm that any of the following products is enclosed Model Description Quantity A1SJ72QLP25 Model A1SJ72QLP25 MELSECNET 10 network module optical loop type 1 A1SJ72QLR25 Model A1SJ72QLR25 MELSECNET 10 network module coaxial loop type 1 Model A1SJ72QBR15 MELSECNET 10 network module coaxial b...

Страница 8: ...station 1 Remote I O stations 64 Overall distance 30km Station to station distance 1 SI optical cable 500m H PCF optical cable 1km Broad band H PCF optical cable 1km QSI optical cable 1km Error control method Retry by CRC X16 X12 X5 1 and overtime RAS function y Loop back function due to abnormality detection and cable disconnection y Diagnostic function for local link circuit check y Abnormality ...

Страница 9: ...er network Remote master station 1 Remote I O stations 64 Remote master station 1 Remote I O stations 32 3C 2V 19 2km 300m 3C 2V 300m 300m 5C 2V 30km 500m 5C 2V 500m 500m Overall distance Station to station distance 1 Can be extended to 2 5km when used with a repeater module A6BR10 A6BR10 DC Error control method Retry by CRC X16 X12 X5 1 and overtime RAS function y Loop back function due to abnorm...

Страница 10: ...circuit or malfunction due to the breakage of a screw or the module z Completely turn off the externally supplied power used in the system before mounting or removing the module Not doing so could result in damage to the product z Do not directly touch the printed circuit board the conducting parts and electronic parts of the module It may cause damage or erroneous operation z Before handling the ...

Страница 11: ... RESET STATION NO X10 X1 MODE FRONTSIDE R SD F RD F SD R RD IN OUT MODE 0 ONLINE A R 2 OFFLINE SW 1 2 3 4 5 Setting OFF OFF QnA ON A F L R L SW 1 2 3 4 5 L R DISPLAY OFF ON A1SJ72QBR15 RUN D LINK T PASS WAIT PW HOLD RMT E SW E ST E PRM E CRC OVER AB IF TIME DATA UNDER SD RD E R R O R RESET STATION NO X10 X1 MODE MODE 0 ONLINE A R 2 OFFLINE SW 1 2 3 4 5 Setting OFF OFF QnA ON A SW 1 2 3 4 5 L R DIS...

Страница 12: ...ost station SW E Incorrect setting of switches 3 and 4 ST E Station number or remote master station status is duplicated on the same network PRM E y When I O allocation is abnormal y When the number of LB LW points is insufficient special function module y When the parameters received from the remote master station are abnormal R E Reverse loop R LOOP is faulty Cause Power off of adjacent station ...

Страница 13: ...s ON Mode setting factory setting at time of shipping 0 Mode Name Contents 0 Online automatic online return effective Data link with automatic online return effective 1 Not used Setting to this turns on the SW E LED 2 Offline Disconnects the host station 3 Forward loop test Checks the forward loop of the whole network system 4 Reverse loop test Checks the reverse loop of the whole network system 5...

Страница 14: ...display is set to valid RUN to F E display is invalid Operation condition setting factory setting at the time of shipping all off SW OFF ON 1 Peripheral device for QnA series connected Peripheral device for A series connected 2 3 4 6 1 Conditions setting switch 5 Not used always off 7 RS 422 interface Connects the peripheral device 8 Connector A1SJ72QLP25 Connect the optical fiber cable IN Reverse...

Страница 15: ...upply is ON reset using the reset switch in 2 2 The setting range for the A1SJ72QBR15 is shown below Setting range 1 to 32 Station number Other than 1 to 32 Setting error The SW E LED turns ON Note that it does not turn ON when set to any of 33 to 64 ...

Страница 16: ...age z When removing the communication cable or power cables from the module do not pull the cable When removing the cable with a connector hold the connector on the side that is connected to the module When removing the cable connected to the terminal block first loosen the screws on the terminal block Pulling the cable that is still connected to the module may cause malfunction or damage to the m...

Страница 17: ...IN FRONT SIDE OUT 0 51 0 39 RUN D LINK T PASS WAIT DUAL F E Unit mm in 1 Please confirm details to Mitsubishi Electric System Service Corporation 6 2 A1SJ72QLR25 A1SJ72QLR25 PW HOLD RMT E SW E ST E PRM E CRC OVER AB IF TIME DATA UNDER SD RD E R R O R RESET STATION NO X10 X1 MODE FRONTSIDE R SD F RD F SD R RD IN OUT MODE 0 ONLINE A R 2 OFFLINE SW 1 2 3 4 5 Setting OFF OFF QnA ON A F L R L SW 1 2 3 ...

Страница 18: ...T E PRM E CRC OVER AB IF TIME DATA UNDER SD RD E R R O R RESET STATION NO X10 X1 MODE MODE 0 ONLINE A R 2 OFFLINE SW 1 2 3 4 5 Setting OFF OFF QnA ON A SW 1 2 3 4 5 L R DISPLAY OFF ON At the time of installation of F type connector 12 3 0 48 12 7 0 5 130 5 12 54 5 2 15 93 6 3 96 Unit mm in ...

Страница 19: ...13 MEMO ...

Страница 20: ...es Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B V French Branch 25 Boulevard des Bouvets F 92741 Nanterre Cedex France TEL 33 1 5568 5568 South Africa Circuit Breaker Industries Ltd Private Bag 2016 ZA 1600 Isando South Africa Tel 27 11 928 2000 Hong Kong Mitsubishi Electric Automation Hong Kong Ltd 10th Floor Manulife Tower 169 Electric Road North Point Hong Kong Tel 852...

Отзывы: