6.10 Setting of Output (Y) Status when Changing between STOP and RUN
6
FUNCTIONS
6.10 Setting of Output (Y) Status when Changing between STOP and
RUN
(1) Definition
When changed from the RUN status to the STOP status, the CPU module stores the
output (Y) in the RUN status into the PLC and turns all outputs (Y) OFF.
Status when changing from STOP to RUN can be selected from the following two
options with parameters in GX Developer.
• The output (Y) status prior to STOP is output.
• The output (Y) is cleared.
(2) Setting applications
Using a holding circuit or similar, it is possible to select whether the output is resumed
from the previous status or not when the STOP status is changed to the RUN status.
• When the output (Y) status prior to STOP is set to output
• When output (Y) is set to clear
Diagram 6.18 Holding circuit
Diagram 6.19 Timing chart when output (Y) status prior to STOP is set to output
Diagram 6.20 Timing chart when output (Y) is set to clear
Start
button
Stop
button
X100
Y110
X102
Y110
OFF
ON
ON
ON
OFF
X102
Y110
X100
RUN
RUN
STOP
STOP
OFF
ON
ON
ON
OFF
X102
Y110
X100
RUN
RUN
STOP
STOP