5 SYSTEM CONFIGURATION
5.1 Precautions for System Configuration
Using terminal block converter module and dedicated cables
The temperature control module measures temperatures based on the temperature of the terminal block. Thus, depending on
the system configuration used, the temperature distribution of the terminal block is not uniform due to the effects of heat
generated from modules, and the measured temperature may greatly differ from the actual temperature. (especially when two
or more temperature control modules are connected next to each other or the temperature control module is mounted next to
the power supply module or CPU module).
In such cases, using the following terminal block converter module and dedicated cables reduces an error caused by the heat
generated.
Precautions
When using the terminal block converter module for temperature control and the temperature control dedicated cable with Q
terminal block, set a thermocouple type for input ranges of all channels.
(1): Remove the provided terminal block, and install the terminal block of the dedicated cable instead.
(2): Temperature control dedicated cable with Q terminal block
(3): Terminal block converter module for temperature control
(4): Thermocouple or compensation conductor
Item
Model
Manufacturer
Temperature control dedicated cable with Q
terminal block
FA-CBLQ64TC** (**: Cable length)
Your local Mitsubishi Electric sales office or
representative
Terminal block converter module for temperature
control
FA-TB20TC
(2)
(4)
(3)
(1)
Содержание MELSEC iQ-R series
Страница 2: ......
Страница 13: ...11 MEMO ...
Страница 15: ...13 CONTENTS TRADEMARKS 82 ...
Страница 19: ...1 PART NAMES 17 1 MEMO ...
Страница 28: ...26 4 PROCEDURES BEFORE OPERATION MEMO ...
Страница 52: ...50 6 INSTALLATION AND WIRING 6 5 Unused Channel Setting MEMO ...
Страница 79: ...APPENDIX Appendix 1 External Dimensions 77 A MEMO ...
Страница 81: ...I 79 MEMO ...
Страница 85: ......