APPX
Appendix 4 Buffer Memory Areas
167
A
CH1 Offset setting value
As Channel change request (Un\G70, b11) is turned off
→
on
→
off in offset/gain setting mode, the measured temperature value
is corrected by a value written in this area.
Specify the value of a 16-bit signed binary number.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
*1 In the case of FX2N allocation mode, only thermocouple K, J and T are setting enabled.
Setting a value out of the range causes an offset/gain temperature setting value range error (error code: 1EC
H).
'CH1 Offset setting value' (Un\G562) and 'CH1 Gain setting value' (Un\G564) must be set to be within the following
temperature input range:
• Offset setting value < Gain setting value
A channel where the set value is out of the above range causes an offset/gain temperature setting value setting error (error
code: 1E9
H).
■
Default value
The default value is set to 0.
• An effective way to achieve high accuracy is to set up error correction in 'CH1 Offset setting value'
(Un\G562) and 'CH1 Gain setting value' (Un\G564) assuming the minimum and maximum temperatures of
the used range.
• Configure 'CH1 Offset setting value' (Un\G562) and 'CH1 Gain setting value' (Un\G564) while reading out
digital output values.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Offset setting value
562
762
962
1162
1362
1562
1762
1962
CH
Offset setting value (In FX2N allocation mode function)
1291
1292
1293
1294
1295
1296
1297
1298
Input type
Input range
Celsius/Fahrenheit display
setting
Setting range
Resistance temperature detector
Pt100
Celsius
-2000 to +8500
Fahrenheit
-3280 to +15620
Ni100
Celsius
-600 to +2500
Fahrenheit
-760 to +4820
Thermocouple
Thermocouple K
Celsius
-2700 to +13700
Fahrenheit
-4540 to +24980
Thermocouple J
Celsius
-2100 to +11300
Fahrenheit
-3460 to +20660
Thermocouple T
Celsius
-2700 to +4000
Fahrenheit
-4540 to +7520
Thermocouple B
Celsius
0 to 17100
Fahrenheit
320 to 31100
Thermocouple R
Celsius
-500 to +17100
Fahrenheit
-580 to +31100
Thermocouple S
Celsius
-500 to +17100
Fahrenheit
-580 to +31100