602
7 APPLICATION INSTRUCTION
7.20 Timing check instruction
• When the command input is set to ON, the operation is started. The special relay of the timing clock output destination is
set to ON or OFF by the END instruction. Even if the command input is set to OFF, the operation is not stopped. In the
STOP mode, the operation is stopped. When the power to the CPU module is turned OFF, the operation is stopped.
• When (n1) and (n2) are set to "0", the status is as shown below:
• The table below shows the related devices.
Precautions
• The DUTY instruction can be used up to 5 times (points). It is not permitted, however, to use the same timing clock output
destination device for two or more DUTY instructions.
Operation error
Status of (n1) and (n2)
ON/OFF status of (d)
(n1)=0, (n2)
0
(d)= Fixed to OFF
(n1)>0, (n2)=0
(d)= Fixed to ON
Special relay
Name
Description
SM420(SM8330)
Timing clock output 1
Timing clock output in the DUTY instruction
SM421(SM8331)
Timing clock output 2
SM422(SM8332)
Timing clock output 3
SM423(SM8333)
Timing clock output 4
SM424(SM8334)
Timing clock output 5
Special register
Name
Description
SD8330
Counted number of scans for timing clock output 1
Counted number of scans for timing clock output 1 in the DUTY
instruction
SD8331
Counted number of scans for timing clock output 2
Counted number of scans for timing clock output 2 in the DUTY
instruction
SD8332
Counted number of scans for timing clock output 3
Counted number of scans for timing clock output 3 in the DUTY
instruction
SD8333
Counted number of scans for timing clock output 4
Counted number of scans for timing clock output 4 in the DUTY
instruction
SD8334
Counted number of scans for timing clock output 5
Counted number of scans for timing clock output 5 in the DUTY
instruction
Error code
(SD0/SD8067)
Description
2820
The device specified by (d) is out of the range from SM420 to SM424 (SM8330 to SM8334).
Содержание MELSEC iQ-F FX5 series
Страница 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Страница 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Страница 438: ...436 7 APPLICATION INSTRUCTION 7 7 Real Number Instruction Operation error There is no operation error ...
Страница 705: ...15 TYPE CONVERSION FUNCTIONS 15 13 Converting DWORD to WORD 703 15 Operation error There is no operation error ...
Страница 707: ...15 TYPE CONVERSION FUNCTIONS 15 14 Converting DWORD to INT 705 15 Operation error There is no operation error ...
Страница 722: ...720 15 TYPE CONVERSION FUNCTIONS 15 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Страница 855: ...26 COUNTER FUNCTION BLOCKS 26 3 Counter Function Block 853 26 Operation error There is no error ...
Страница 887: ......