7 APPLICATION INSTRUCTION
7.9 Index register operation instruction
469
7
Saving the selected data of the index register and long index
register
ZPUSH(P)
These instructions save the contents of index registers and long index registers within the range specified by (s) in the devices
specified by (d) and later.
Setting data
■
Descriptions, ranges, and data types
■
Applicable devices
Processing details
• These instructions save the contents of index registers and long index registers within the range specified by (s) in the
devices specified by (d) and later. The type of the index register or long index register saved is stored in the end of the
saved data.
• When the contents of the index registers and long index registers are saved, "1" is added to (d).
• The following shows values specified by (s) and the index register or long index register to be saved.
• The selected data of index register/long index register return instructions (ZPOP(P) instructions) are used to return the
data. The selected data of index register/long index register save instructions (ZPUSH(P) instructions) and the selected
data of index register/long index register return instructions (ZPOP(P) instructions) can be used in pairs and to adopt a
nesting structure. (
Page 471 Returning the selected data of the index register and long index register)
• When a nesting structure is adopted, the areas to be used are added to (d) and later every time the selected data of index
register/long index register save instructions (ZPUSH(P) instructions) are executed. Check the number of index registers
and long index registers by SD300 and SD302, and secure the areas for the number of instructions to be used in advance.
Ladder diagram
Structured text
ENO:=ZPUSH_2(EN,s,d);
ENO:=ZPUSHP_2(EN,s,d);
Operand
Description
Range
Data type
Data type (label)
(s)
Type of the index register or long index register to be saved
0 to 2
16-bit unsigned binary
ANY16
(d)
Head device number for saving the data of index registers
16-bit signed binary
ANY16
Operand
Bit
Word
Double word
Indirect
specification
Constant
Others
X, Y, M, L,
SM, F, B, SB
U
\G
T, ST,
C, LC
T, ST, C, D,
W, SD, SW, R
U
\G
Z
LC
LZ
K, H
E
$
(s)
(d)
(s) value
Z or LZ to be saved
0
Z, LZ (whole range)
1
Z (whole range)
2
LZ (whole range)
(s)
(d)
Содержание MELSEC iQ-F FX5 series
Страница 1: ...MELSEC iQ F FX5 Series Programming Manual Instructions Standard Functions Function Blocks ...
Страница 2: ......
Страница 21: ...19 PART 1 PART 1 OVERVIEW Part 1 consists of the following chapter 1 OVERVIEW ...
Страница 98: ...96 4 STANDARD FUNCTIONS FUNCTION BLOCKS 4 2 Standard Function Blocks MEMO ...
Страница 438: ...436 7 APPLICATION INSTRUCTION 7 7 Real Number Instruction Operation error There is no operation error ...
Страница 705: ...15 TYPE CONVERSION FUNCTIONS 15 13 Converting DWORD to WORD 703 15 Operation error There is no operation error ...
Страница 707: ...15 TYPE CONVERSION FUNCTIONS 15 14 Converting DWORD to INT 705 15 Operation error There is no operation error ...
Страница 722: ...720 15 TYPE CONVERSION FUNCTIONS 15 26 Converting DINT to WORD Operation error There is no operation error ...
Страница 840: ...838 23 TIME DATA FUNCTIONS 23 4 Division MEMO ...
Страница 855: ...26 COUNTER FUNCTION BLOCKS 26 3 Counter Function Block 853 26 Operation error There is no error ...
Страница 887: ......