8. OPTIONAL PARTS
8-3. Joint Adapter Kit
Joint adapter kit “CMY-R160C-J” is used to combine two ports of the BC controller for a PURY-HP-T(S)KMU/Y(S)KMU system to enable
Indoor capacity above P54 as shown in Fig. 1.
2 - 477
7. OPTIONAL PARTS
DATA U10
OUTDOOR UNITS
H
2i
R
2
7-3. JOINT KIT CMY-R160C-J FOR BC CONTROLLER
Joint kit "CMY-R160C-J" is used to combine two ports of the BC controller for a PURY-HP-T(S)KMU/Y(S)KMU system to enable
Indoor capacity above P54 as shown in Fig. 1.
2. Piping at the installation site
Refer to Fig. 2 for connecting the CMY-R160C-J to the BC controller and the pipe leading to the Indoor units. Non-oxidized brazing
is necessary. Avoid getting foreign material inside the piping.
After piping and air-tight testing, insulate the joint and pipe. Details are available in the Installation Manual.
1pc
1pc
1pc
2pcs
1pc
1pc
8pcs
2pcs
(for liquid side)
The Joint kit include following items:
(for gas side)
(for gas side)
(for liquid side)
1 Instructions
2 Joint pipe
3 Joint pipe
4 Cover 1
5 Cover 2
6 Cover 3
7 Band
8 Reducer
2 Joint pipe (for liquid side)
3 Joint pipe (for gas side)
in.(mm)
2-3/8"(60)
2-3/8"(60)
1. Designing CMY-R160C-J to a PURY-HP-T(S)KMU/
Y(S)KMU system
The maximum of Indoor capacity for one port of BC controller
is P54. When the Indoor capacity is above P54, Joint kit CMY-
R160C-J is needed to combine two ports of BC controller to en-
large the capacity, like Groups 2 and 3 in Fig. 1.
A maximum of three Indoor units are allowed to connect to one
port of BC controller or two combined ports of BC controller us-
ing CMY-R160C-J.
When connecting Indoor units to one port of BC controller or
two combined ports of BC controller using CMY-R160C-J,
CMY-Y102SS-G2 or CMY-Y104C-G is applicable, like Groups
1 and 2 in Fig. 1
Caution: Simultaneous operation of cooling and heating
modes for Indoor units connecting to the same BC ports is not
available.
PURY-HP-T(S)KMU/Y(S)KMU
Joint kit
CMY-R160C-J
CMY-Y102SS-G
BC controller
Fig.1. CMY-R160C-J applying scheme
IU
IU
IU
IU
IU
OU
IU
IU
Group1
Total Indoor Capacity
<=P54
Group2
Total Indoor Capacity
P55 to P96
Group3
Total Indoor Capacity
P72 or P96
Clamping torque 35N•m
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Clamping torque 80N•m
Use two spanners simultaneously for tightening.
Coat the flare contact surface with refrigerating machine oil.
Piping to indoor unit
(Non-oxidized brazing)
Joint pipe (for liquid side)
2
Joint pipe(for gas side)
3
Flare nut 5/8" (15.88)
Flare nut 3/8" (9.52)
Fig.2. Connecting CMY-R160C-J