7. CAPACITY TABLES
7-4-25. Heating Capacity [Intelligent Heat Mode] with PURY-HP72TKMU-A-H (cont.)
6. CAPACITY TABLES
DATA U10
OUTDOOR UNITS
2 - 428
H
2i
R
2
70
-13.0
41900
23100
41900
23900
41900
24300
40200
23600
-9.0
44700
23400
44700
24200
44700
24800
40200
22400
-4.0
48300
23800
48300
24500
46900
24700
40200
20800
1.0
51900
24200
51900
25000
46900
22900
40200
19300
5.0
54800
24600
54700
25500
46900
21600
40200
18200
10.0
58300
25000
55900
24700
46900
20000
40200
16800
14.0
56600
22400
49500
20000
46900
18800
40200
15800
19.0
55900
20000
47500
17500
46900
17400
40200
14600
23.0
55900
18900
47500
16500
46900
16300
40200
13700
28.0
61700
20300
53700
17200
46900
15100
40200
12700
32.0
63700
20200
55900
17100
46900
14100
40200
11900
37.0
63700
18600
55900
15700
46900
13100
40200
11000
41.0
63700
17400
55900
14700
46900
12300
40200
10300
43.0
63700
16900
55900
14400
46900
11900
40200
10000
46.0
63700
16000
55900
13700
46900
11400
40200
9600
50.0
63700
15000
55900
13000
46900
10800
40200
9000
55.0
66300
15200
55900
12300
46900
10100
40200
8400
59.0
69300
15200
55900
11900
46900
9600
40200
7900
60
-13.0
35900
19900
35900
20600
35900
20900
34500
20400
-9.0
38300
20200
38400
20800
38300
21400
34500
19300
-4.0
41400
20600
41400
21200
40200
21300
34500
17900
1.0
44500
20900
44500
21600
40200
19700
34500
16600
5.0
46900
21200
46900
22000
40200
18600
34500
15700
10.0
50000
21500
47900
21300
40200
17200
34500
14500
14.0
48500
19300
42400
17300
40200
16200
34500
13600
19.0
47900
17200
40700
15100
40200
15000
34500
12600
23.0
47900
16300
40700
14200
40200
14100
34500
11800
28.0
52900
17500
46000
14900
40200
13000
34500
10900
32.0
54600
17400
47900
14700
40200
12200
34500
10300
37.0
54600
16000
47900
13500
40200
11300
34500
9500
41.0
54600
15000
47900
12700
40200
10600
34500
8900
43.0
54600
14500
47900
12400
40200
10300
34500
8600
46.0
54600
13800
47900
11800
40200
9800
34500
8200
50.0
54600
13000
47900
11200
40200
9300
34500
7800
55.0
56800
13100
47900
10600
40200
8700
34500
7200
59.0
59400
13100
47900
10300
40200
8300
34500
6800
50
-13.0
29900
17000
29900
17600
29900
17900
28700
17400
-9.0
32000
17300
32000
17800
32000
18300
28700
16500
-4.0
34500
17600
34500
18100
33500
18200
28700
15300
1.0
37100
17900
37100
18400
33500
16900
28700
14200
5.0
39100
18100
39100
18800
33500
15900
28700
13400
10.0
41700
18400
39900
18200
33500
14700
28700
12400
14.0
40400
16500
35400
14800
33500
13800
28700
11700
19.0
39900
14700
33900
12900
33500
12800
28700
10800
23.0
39900
14000
33900
12100
33500
12000
28700
10100
28.0
44100
14900
38400
12700
33500
11100
28700
9300
32.0
45500
14900
39900
12600
33500
10400
28700
8800
37.0
45500
13700
39900
11500
33500
9600
28700
8100
41.0
45500
12800
39900
10900
33500
9100
28700
7600
43.0
45500
12400
39900
10600
33500
8800
28700
7400
46.0
45500
11800
39900
10100
33500
8400
28700
7000
50.0
45500
11100
39900
9600
33500
7900
28700
6600
55.0
47300
11200
39900
9100
33500
7400
28700
6200
59.0
49500
11200
39900
8800
33500
7100
28700
5900
PURY-HP72TKMU-A-H
TC:Total Capacity(BTU), PI:Power Input(BTU)
Combination
Outdoor
Indoor air temp.
(%)
air temp.
59°F D.B.
70°F D.B.
77°F D.B.
81°F D.B.
°F W.B.
TC
PI
TC
PI
TC
PI
TC
PI
kcal/h=kW x 860 , BTU/h = kW x 3,412