– 4 –
5
Installation method
1. Parts prepared at site
1
Prepare an electric box.
2
Prepare lock nuts and bushing that match the conduit.
3
Prepare an M-NET transmission line CVVS(2-wire):
1.25mm
2
or equivalent.
4
DC power supply line (3-conductor): Provide
0.75mm
2
or greater.
2. Installation method
1
Secure the space shown on the right when installing the electric box.
2
When installing the controller on the electric box, the controller will be shifted by 1mm to the left as shown above.
NOTE
* When installing two controllers horizontally in parallel, secure a clearance of 30mm or more between the products.
When installing vertically with the same clearance, removing of the cover will be difficult.
* When connecting a LAN and RS-232C, a space for the connector and wiring is required. Provide this space between this unit
and the rear of the electric box.
It varies depending on the specifications of the LAN cable and RS-232C cable that is procured, but the LAN connector may
protrude approximately 20mm and the RS-232C connector may protrude approximately 40mm from the bottom of the unit cabinet.
Provide a cable with the smallest possible connector to secure space.
Reference example) Example of installation when a 67mm deep electric box is used with a 30mm thick wall.
3
Connect the M-NET transmission line (centralized control line which is connected to TB7 of the outdoor unit) to M-NET transmis-
sion line terminal A and B. (Non Polarity)
Connect the DC power line from the power supply unit (PAC-SC50KUA) to the DC power supply terminal block of this device.
There is a 12VDC and a GND polarity.
* Type of wire. Use the cables which comply with the following specifications or equivalent.
M-NET transmission line:
CVVS
1.25mm
2
(PVC-insulated, PVCsheathed shield control cable)
CPEVS
ø1.2mm (PE-insulated, PVC-sheathed shield communication cable)
DC power line: 0.75mm
2
or greater 3-conductor power line
CAUTION
* Do not connect the AC power line to the M-NET and
POWER (DC12V) terminal blocks of this device. It may
cause a failure.
* Do not connect to the M-NET transmission line of indoor
unit control line which is connected to TB3 of the outdoor
unit.
* The conduit outlet faces only vertically. When leading the
line out from above, seal the port so that water does not
enter along the transmission line and DC power supply
line.
4
Securely seal the line lead-in port with putty to prevent the
entry of dew, water and insects, etc.
* Seal the connecting section of the electric box and conduit with
putty.
Center of electric box
Electric box
(Shaded section)
Center the controller
The controller outline
Clearance around the controller
Conduit
Lock nut
Electric box
Seal with putty
Bushing
M-NET transmission line
and DC power line
Wall
Controller rear surface
When not using
bridge wiring
*When using bridge wiring of the shield,
use the S-terminal as shown below.
M-NET transmission line
DC power line
POWER
GND
12VDC
A
B
S
M-NET
57
mm
30mm
67mm
Wall
Electric box
RS-232C cable
LAN cable
Radiated noise suppressor when RS-232C cable used.
(Model: PAC-YG11FC-E)
Approx.
40mm
Central controller
Содержание G-50A