314
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9 CC-Link/LT Built-in master ability (Only FX3UC-32MT-LT)
9.18 Details of buffer memory
FX
3UC
Series Programmable Controllers
User’s Manual - Hardware Edition
9.18.10 Status information [BFM #28 (1Ch)]
Status information such as RUN and link status are stored here.
1. Detailed description
The status is indicated by the 0 (OFF)/1 (ON) status of each bit.
Initial communication:
When the power to the PLC is set to ON, the PLC acquires information on connected remote stations from the
built-in master.
9.18.11
Detailed error information [BFM #29 (1Dh)]
1. Detailed description
The status is indicated by the 0 (OFF)/1 (ON) status of each bit.
Bit
Function
Description
b0
Data link status
Remains ON while the I/O image in the built-in master is updated by the
data link.
b1
Initial communication status
Turns ON when acquisition of the remote station information is
completed.
b2
RUN status
Remains ON while the unit is operating normally.
(Indicates the same contents as the LED.)
b3
CONFIG mode
Remains ON while CONFIG mode is selected.
b4
EEPROM write completion
Turns ON when write to the EEPROM is completed, then turns OFF
when write is completed and the write request flag [BFM #27 (1Bh) b4]
is set to OFF.
b5
Data link stopped
Remains ON while the data link is stopped by the request to stop data
link.
b6 to b15
-
Prohibited to use
Bit
Function
Description
Error flag restoration operation
b0
Link error in
some stations
Turns ON when link error has occurred in
some stations. [Turns ON when any bit in
BFM #4 (4h) to 7 (7h) have turned ON.]
For the station number in which the error has
occurred, refer to the link error station
information [BFM #4 (4h) to 7 (7h)].
When the cause of the error is eliminated,
the error flag is automatically restored.
b1
Link error in all
stations
Turns ON when data link error has occurred
in all stations.
When the cause of the error is eliminated,
the error flag is automatically restored.
b2
Remote I/O
error
Turns ON when remote I/O error has
occurred. [Turns ON when any bit in BFM #8
(8h) to 11 (Bh) have turned ON.]
For the station number, refer to the remote
I/O error information [BFM #8 (8h) to 11
(Bh)].
For the type of error, refer to the instruction
manual of the appropriate remote station.
When the cause of the error is eliminated,
the error flag is automatically restored.
b3
Out-of-
control-range
station error
Turns ON when a remote station not
registered in the detailed remote station
information [BFM #32 (20h) to #95 (5Fh)] is
connected to the network.
If the station number of the connected
remote station is smaller than the final
station number, the error flag is
automatically restored when the cause of
the error is eliminated.
If the station number of the connected
remote station is larger than the final
station number, the error flag is restored
when the cause of the error is eliminated
and is followed by a power reset.
b4
Transmission
speed setting
error
Turns ON when the transmission speed
setting DIP switch is set to an incompatible
position.
When the cause of the error is eliminated,
and power is reset, the error flag is
automatically restored.
b5
-
Prohibited to use
-