FX Series Computer Link Driver
GP-Pro EX Device/PLC Connection Manual
18
Device Setting
To display the setting screen, touch [Device/PLC Settings] from [Peripheral Settings]. Touch the External Device
you want to set from the displayed list, and touch [Device].
Wait To Send
Use an integer from 0 to 255 to enter standby time (ms) for Display from receiving packets to
transmitting next commands.
Set the value more than twice as the scanning time of External Device when connecting to
FX0N, FX1S, FX1N and FX1NC Series.
Setup Items
Setup Description
Device/PLC Name
Select the External Device for device setting. Device name is a title of External Device set
with GP-Pro EX.(Initial value [PLC1])
Station No.
Enter a station number of the External Device, using 0 to F.
Setup Items
Setup Description