background image

This manual confers no industrial property rights or any rights of any other kind, 
nor does it confer any patent licenses. Mitsubishi Electric Corporation cannot be 
held responsible for any problems involving industrial property rights which may 
occur as a result of using the contents noted in this manual.

Warranty

Mitsubishi will not be held liable for damage caused by factors found not to be 
the cause of Mitsubishi; opportunity loss or lost profits caused by faults in the 
Mitsubishi products; damage, secondary damage, accident compensation 
caused by special factors unpredictable by Mitsubishi; damages to products 
other than Mitsubishi products; and to other duties.

For safe use

This product has been manufactured as a general-purpose part for general 
industries, and has not been designed or manufactured to be incorporated in 
a device or system used in purposes related to human life.
Before using the product for special purposes such as nuclear power, electric 
power, aerospace, medicine or passenger movement vehicles, consult with 
Mitsubishi Electric.
This product has been manufactured under strict quality control. However 
when installing the product where major accidents or losses could occur if the 
product fails, install appropriate backup or failsafe functions in the system.

HEAD OFFICE

HIMEJI WORKS

 : TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, 
   JAPAN
 : 840, CHIYODA CHO, HIMEJI, JAPAN

3. Installation

The extension block can be installed on a DIN46277 rail (35 mm (1.38") wide).
(Cannot be installed directly in the enclosure.)
For details, refer to the FX

3UC

 Series User's Manual - Hardware Edition.

4. Example Wiring

For details, refer to the FX

3UC

 Series User's Manual - Hardware Edition.

INSTALLATION 
PRECAUTIONS

Use the product within the generic environment specifications described in

PLC main unit manual (Hardware Edition).
Never use the product in areas with excessive dust, oily smoke, conductive

dusts, corrosive gas (salt air, Cl

2

, H

2

S, SO

2

, or NO

2

), flammable gas,

vibration or impacts, or exposed to high temperature, condensation, or rain

and wind.
If the product is used in such conditions, electric shock, fire, malfunctions,

deterioration or damage may occur.

Make sure to cut off all phases of the power supply externally before attempt-

ing installation or wiring work.
Failure to do so may cause electric shock.

Use screwdrivers carefully when performing installation work, thus avoiding 
accident or product damage.

When drilling screw holes or wiring, make sure cutting or wire debris does 
not enter the ventilation slits.

Failure to do so may cause fire, equipment failures or malfunctions.

WIRING 
PRECAUTIONS

Make sure to cut off all phases of the power supply externally before
attempting installation or wiring work.
Failure to do so may cause electric shock or damage to the product.

WIRING 
PRECAUTIONS

Connect the DC power supply wiring to the dedicated terminals specified in
this manual. If an AC power supply is connected to a DC input/output
terminal or DC power supply terminal, the PLC will burn out.

Connect the AC power supply wiring to the dedicated terminals specified in
this manual. If an AC power supply is connected to a DC input/output
terminal or DC power supply terminal, the PLC will burn out.

Do not wire vacant terminals externally.
Doing so may damage the product.

Perform class D grounding (grounding resistance: 100

 or less) to the

grounding terminal on the main unit.
Do not use common grounding with heavy electrical systems (refer to the
manual of the PLC main unit).

When drilling screw holes or wiring, make sure cutting or wire debris does
not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.

4.1 Input

4.2 Output

4.2.1

Transistor Output Type

No.

Description

External power supply 24V DC +20% -15%

Breaker, Circuit protector, Fuse etc.

Fuse

MPU main processing unit (main unit)

Class D grounding (grounding resistor 100

 or less)

FX

2NC

 Extension block

Contact

Three wire sensor

No.

Description

FX

2NC

 Extension block

DC power supply

Emergency stop

Fuse

Load

COM X000 X001

COM

1

2

3

4

6

7

8

5

1

2

3

4

5

6

7

8

COM1

COM1

Y000

Y001

Y002

1

2

3

4

5

5

5

1

2

3

4

5

4.2.2

Relay Output Type

No.

Description

FX

2NC

 Extension block

AC power supply

Emergency stop

Fuse

Load

COM1

COM1

Y000

Y001

Y002

1

2

3

4

5

5

5

1

2

3

4

5

Отзывы: