DETAILS OF INPUT AND
OUTPUT SIGNALS
7
RWr4
Third monitor value
When RYC is on, the monitor value specified to the monitor code (RWw
) is stored.
(
indicates a register number (RWw4 to 7)
RWr5
Fourth monitor value
RWr6
Fifth monitor value
RWr7
Sixth monitor value
RWr8
Alarm definition
(alarm data)
The alarm data of alarm definition No. specified by RWw8 is stored in the lower 8bits.
Alarm definition No. specified is echo backed to the upper 8bits.
RWr9
Alarm definition
(output frequency)
Output frequency of the alarm definition No. specified in RWw8 is stored.
RWrA
Alarm definition
(output current)
Output current of the alarm definition No. specified in RWw8 is stored.
RWrB
Alarm definition
(output voltage)
Output voltage of the alarm definition No. specified in RWw8 is stored.
RWrC
Alarm definition
(energization time)
Energization time of the alarm definition No. specified in RWw8 is stored.
RWr10
to
RWr19
Reply code
Turning on RYF stores the reply code corresponds to the instruction code of RWw10,
12, 14, 16, and 18. The value "0" is set for a normal reply and other than "0" is set for
data fault, mode error, etc.
(reply code
refer to page 66)
Read data
For a normal reply, the reply data to the instruction specified by the instruction code is
set.
Device
No.
Signal
Description