OC292-27
Control modes
Control details
3. Drain pump
Except for
PKFY-08NAMU-A.
1. Thermoregulating
function
Remarks
2. Fan
4. Vane
(up/ down vane change)
Same control as COOL operation
Same control as COOL operation
1-1. Thermoregulating function (Function to prevent restarting for 3 minutes)
Setting the Dry thermo by the thermoregulating signal and the
room temperature (TH1).
Dry thermo ON Room temperature
]
desired tempe 2
°
F
Dry thermo OFF Room temperature
[
desired temperature
1-2. Frozen prevention control
No control function
Indoor fan operation controlled depends on the compressor conditions.
Room
temperature
3 min. passed since starting operation
Thermoregulating signal Room temperature (T1)
Dry thermo
ON
time (min)
Dry thermo
OFF
time (min)
Less than 64
°
F
Over 64
°
F
ON
OFF
T1
]
82
°
F
82
°
F > T1
]
79
°
F
79
°
F > T1
]
75
°
F
75
°
F > T1
Unconditional
9
3
7
3
5
3
3
3
10
3
Dry thermo OFF
Note: Remote controller setting is not acceptable.
Dry thermo
Fan speed notch
ON
OFF
[Low]
Stop
8-2. DRY operation
<How to operate>
1
Press POWER ON/OFF button.
2
Press the operation MODE button to display DRY.
3
Press the SET TEMP. button to set the desired temperature.
NOTE: The set temperature changes 2°F when the or button is
pressed one time. Dry 67 to 87°F.