3 - 12
MELSEC-A
3 SPECIFICATION
Table 3.6 Remote I/O Signal Details (2/2)
Device No.
Signal Name
Description
RYn0
to
RYn1
CH.
analog output
enable/disable flag
D/A conversion value output enable flag for channel 1 or 2. Turn on this flag to
enable the D/A conversion value of the corresponding channel to be output.
Turn off when you want to disable the output of the D/A conversion value.
Processed on the leading edge of ON/OFF.
RY (n+1) 8
Initial data processing complete
flag
Turns on after initial data processing completion when initial data processing is
requested after power-on or test mode operation.
RY (n+1) 9
Initial data setting request flag
Turns on at the time of initial data setting or changing.
RY (n+1) A
Error reset request flag
Turning on this flag resets (turns off) the error status flag (RX(n+1)A) and also
clears (to 0000
H
) the error code (RWrn+2) and CH.
check code (RWrn,
RWrn+1) in the remote register. However, since the E
2
PROM write error flag
(RXnC) cannot be reset, the error status flag remains on, too.
n: Address allocated to the master module by station number setting.