background image

About This Manual

The following product manuals are available.  Please use this table as
a reference to request the appropriate manual as necessary.

Detailed manual

Manual name

Manual No.

(Model Code)

A1S62TCRT-S2 Heating-Cooling Temperature Control Module
A1S62TCRTBW-S2 Heating-Cooling Temperature Control
Module with Wire Breakage Detection Function User's Manual

SH-3644
(13JL36)

Please read A1S62TCRT-S2 Heating-Cooling Temperature Control Module
A1S62TCRTBW-S2 Heating-Cooling Temperature Control Module with Wire
Breakage Detection Function User's Manual (Detailed edition) when using this
unit.

 1. General Description 

This user's manual describes the specification, name of each part,
wiring, etc. of the A1S62TCRT-S2 Heating-Cooling Temperature Control
Module (Hereafter abbreviated as A1S62TCRT-S2 ) A1S62TCRTBW-S2
Heating-Cooling Temperature Control Module with Wire Breakage
Detection Function (Hereafter abbreviated as A1S62TCRTBW-S2)
A1S62TCRT-S2 and A1S62TCRTBW-S2 abbreviated as A1S62TC.
After unpacking, confirm that there is the following products.

Item

A1S62TCRT-S2

Main body

A1S62TCRTBW-S2

Main body

A1S62TCRT-S2

1

-

A1S62TCRTBW-S2

-

1

 2. Performance Specification 

The A1S62TC performance specification is indicated in Table 2.1.

Table 2.1 A1S62TC performance specification

Specification

Item

A1S62TCRT-S2

A1S62TCRTBW-S2

Control output

Transistor output

Temperature input points

2-channel/module

Supported platinum temperature-
measuring resistor

Refer to Table 2.2.

Ambient temperature:
23

5

Full scale

(

0.3%) 

1 digit*1

Specification
accuracy

Ambient temperature:
0 to 55

Full scale

(

0.7%) 

1 digit*1

Sampling period

0.5s/2-channel (It is not connected with the
number of channels used)

Heating control output period
Cooling control output period

1 to 100s

Sensor current

0.25mA

Allowable input wire resistor effects

Less than 20

Input filter

0 to 100s (0: input filter off)

Sensor compensation value setting

-50.00 to 50.00%

Operation when sensor input is
disconnected

Upscale processing

Temperature control method

PID on/off pulse

PID constant setting

Auto-tuning setting is possible

Heating proportional band
(Ph)
Cooling proportional band
(Pc)

0.1 to 1000.0%

Integral time (I)

1 to 3600s

PID
constant
range

Derivative time (D)

0 to 3600s (0: PI control)

Set value setting range

Within the temperature range set by the
platinum temperature-measuring resistor
to be used.

Cooling method setting

Air cooling/water cooling

Output signal

ON/OFF pulse

Rated load voltage

10.2 to 30.0VDC (peak voltage : 30.0VDC)

Maximum load current

0.1A/1 point
0.4A/common

Maximum inrush current

0.4A 10ms

Maximum current when
OFF

Less than 0.1mA

Maximum voltage drop
when ON

1.0VDC (TYP) 0.1A
2.5VDC (MAX) 0.1A

Transistor
output

Response time

OFF

ON: Less than 2ms

ON

OFF: Less than 2ms (resistor load)

Insulation method

Between the input and grounding:
transformer insulation
Between the input and channel:
transformer insulation

Table 2.1 A1S62TC performance specification (continued)

Specification

Item

A1S62TCRT-S2

A1S62TCRTBW-S2

Current sensor

URD manufactured
current sensor*2
CTL-12-S36-8
(0.0 to 100.0A)
CTL-6-P-H
(0.00 to 20.00A)
(Former model,
CTL-6-P is also
applicable.)

Input method

Multiplex method
A/D conversion

Heater wire
breakage
disconnection
specification

Number of alert
delays

-

3 to 255

I/O occupied points

Special 32 points

Connection terminal

20 points terminal block

Supported cable size (mm) [inch]

0.75 to 1.5 [0.030 to 0.059]

Supported solder-less terminal

R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A

Internal consumed current (5VDC)
[A]

0.19

0.28

Weight (kg) [lb]

0.25 [0.55]

0.28 [0.62]

For the noise resistance, dielectric withstand voltage, and insulation
resistance for the PC system which uses this module, refer to the power
module specification found in the CPU Module User’s Manual.

*1: “

1 digit” error depends on the input range.

For setting unit of 1

1

   For setting unit of 0.1

0.1

*2: Only the URD International, Ltd. current sensor can be used.

Sales channels for current sensors manufactures by URD
International Ltd. are listed as follows:

U.S.A.

Julia Industries Inc.
Tel:949-831-0111

BRAZIL

Ananda Industial Ltda.
Tel:011-5584-0959

UNITED
KINGDOM Omni Components

Tel:024-7622-5757

GERMANY Allied Electronics GmbH

Tel:0221-497-3084

FRANCE

Diltronic S.A.
Tel:01-34-51-33-00

ITALY

ELNET s.n.c.
Tel:041-50-19-939

KOREA

Joyang Trading Co.
Tel:02-521-2294
Sewon Tech Co.,Ltd.
Tel:02-868-9355/9356
Keum Ho Corporation
Tel:51-319-4155/4156

HONG-KONG Weltronics Components Ltd.

Tel:2410-0623

TAIWAN

Tope Co.,Ltd.
Tel:886-2-8228-0658

INDIA

AmtechElectronics PVT.Ltd.
Tel:02712-25324

Table 2.2  The types of supported platinum temperature-measuring

resistor and the measured temperature range

°

F

Platinum

temperature-

measuring

resistor

Measured

temperature

range

Data

resolution

Measured

temperature range

Data

resolution

-300 to 1100

1

Pt 100

-200.0 to 600.0
-200.0 to 200.0

0.1

-300.0 to 300.0

0.1

-300 to 900

1

JPt100

-200.0 to 500.0
-200.0 to 200.0

0.1

-300.0 to 300.0

0.1

For the general specifications, refer to the User’s Manual for the PC
CPU used.

Отзывы: