MITSUBISHI ELECTRIC 7011A SERIES UPS
MITSUBISHI
ELECTRIC
7011A SERIES UPS
OWNERS / TECHNICAL MANUAL
Page Number:
3-8
Wire Connection (208V – 120V WYE, 2 phase, 3wire)
FIGURE 3.6.1
Correct connection
FIGURE 3.6.2
Incorrect connection
-> Code 803 Displayed on LCD when UPS powered up.
UPS Must have Clockwise Phase Rotation if Error code 803 occurs, swap L1 and L2.
(see figure 3.6.1 and 3.6.2)