2.2 Performance Specifications

The performance specifications for the AJ65SBT2B-64RD3 are shown 
in the following table.

Table 2.2 Performance specifications

Item

AJ65SBT2B-64RD3

Measurement method

3-wire

Measured temperature 
value

16-bit signed binary (-2000 to 8500)

Usable RTD

Pt100 (JIS C 1604-1997), JPt100 (JIS C 1604-1981), Ni100 (DIN 

43760 1987)

Detecting current

1mA

Detecting range, degree 
of conversion accuracy, 
resolution

Conversion speed

40ms/1channel

Temperature input point

4 channels/1 module

Maximum number of
writes for Flash memory

MAX. 10,000 times

CC-Link station type

Remote device station

No. of occupied stations

1 station (RX/RY: 32 points each, RWr/RWw: 4 points each)

Connection cable

CC-Link dedicated cable

Withstand voltage

500 V AC for 1 minute across all power supply and communication 

system terminals and all RTD input terminals

Isolation system

Between communication system and all RTD inputs: Photocoupler 
isolation
Between power supply system and all RTD inputs: Trans isolation
Between channels: No isolation

Noise immunity

Noise  voltage : 500Vp-p, tested by noise simulator of noise width of 

1 s and noise frequency of 25 to 60Hz

Wire break detection

Capable (channels respectively) 

Detecting range

Degree of conversion 

accuracy

*1*2

Resolution

Ambient 

temperature

0 to 55

Ambient 

temperature

25 5

Pt100

-200 to 850

1.4

0.5

0.1

-20 to 120

0.6

0.2

0 to 200

0.6

0.2

JPt100

-180 to 600

1.0

0.4

-20 to 120

0.6

0.2

0 to 200

0.6

0.2

Ni100

-60 to 180

0.5

0.2

Содержание 13JY77

Страница 1: ...asing the Mitsubishi programmable controller 2008 MITSUBISHI ELECTRIC CORPORATION RTD Input Module Prior to use please read this and relevant manuals thorougly to fully understand the product MODEL AJ...

Страница 2: ...user s manual In this manual the safety instructions are ranked as DANGER and CAUTION Note that the CAUTION level may lead to a serious consequence according to the circumstances Always follow the in...

Страница 3: ...module in an environment that meets the general specifications given in this manual Operating it in any other environment may cause an electric shock fire malfunction product damage or deterioration F...

Страница 4: ...cted when the terminal screw comes loose resulting in failure Check the rated voltage and terminal layout and then wire the module correctly Connecting a power supply of a different voltage rating or...

Страница 5: ...ing so can cause the module to fail or malfunction Undertightening can cause a drop short circuit or malfunction Overtightening can cause a drop short circuit or malfunction due to damage of the screw...

Страница 6: ...May 2008 IB NA 0800420 A First edition This manual confers no industrial property rights or any rights of any other kind nor does it confer any patent licenses Mitsubishi Electric Corporation cannot...

Страница 7: ...AND SETTINGS 6 3 1 Part Names 6 4 LOADING AND INSTALLATION 9 4 1 Handling Precautions 9 5 DATA LINK CABLE WIRING 11 5 1 Wiring Precautions 11 5 2 CC Link Dedicated Cable Connection Method 11 5 3 Conn...

Страница 8: ...y or equipment refer to the EMC AND LOW VOLTAGE DIRECTIVES chapter of the User s Manual for the CPU module used The CE mark indicating compliance with the EMC and Low Voltage Directives is printed on...

Страница 9: ...his user s manual explains the specifications names of the components and wiring for the type AJ65SBT2B 64RD3 RTD Input Module hereafter AJ65SBT2B 64RD3 which are used as a remote device station of a...

Страница 10: ...atmospheric pressure at the altitude of 0m Doing so may cause a malfunction Please consult our branch office when the programmable controller is to be operated under pressure Table 2 1 General specifi...

Страница 11: ...ion RX RY 32 points each RWr RWw 4 points each Connection cable CC Link dedicated cable Withstand voltage 500 V AC for 1 minute across all power supply and communication system terminals and all RTD i...

Страница 12: ...tightening torque 59 to 88N cm Applicable solderless terminals 2 max Applicable wire size 0 3 to 2 0mm2 Applicable solderless terminals RAV1 25 3 conforming to JIS C 2805 Applicable wire size 0 3 to...

Страница 13: ...conversion accuracy Degree of tolerance of RTD Refer to Table 2 3 1 40 0 15 0 002 800 3 15 Because the resolution is 0 1 3 2 t Measured temperature Table 2 3 Degree of tolerance of RTD Resistance the...

Страница 14: ...6 3 PART NAMES AND SETTINGS 3 1 Part Names This section explains the names of the components for the AJ65SBT2B 64RD3 Figure 3 1 Appearance of the AJ65SBT2B 64RD3...

Страница 15: ...subtracted from the gain value Indicates that the SELECT SET switch is in the SELECT or center position L RUN LED On Normal communication Off Communication cutoff time expiration error L ERR LED On F...

Страница 16: ...32 set the switches as indicated below Use prohibited Set all station number to OFF Terminal block Used to connect the module power supply transmission and analog I O signals DIN rail hook Used to mo...

Страница 17: ...the screw resulting in a short circuit or malfunction When disposing of this product treat it as industrial waste Use the module in an environment that meets the general specifications given in this m...

Страница 18: ...5SBT2B 64RD3 to the DIN rail press with your finger the centerline of the DIN rail hook at the bottom of the module until it clicks Figure 4 1 Installation to DIN rail 4 Refer to the Master Module use...

Страница 19: ...s no need the external wiring 1 Precautions a Move the L TER switch until it clicks b Make sure that between DA and DB is high resistance when the L TER switch is off or is 110 When the L TER switch i...

Страница 20: ...TD at least 10cm away from the main circuit cables and AC control circuit lines Fully keep it away from high voltage cables and circuits which include high frequency waves such as an inverter s load c...

Страница 21: ...ERNAL DIMENSIONS The external dimensions of the AJ65SBT2B 64RD3 is shown below Unit mm inch DIN rail center 109 5 0 5 4 31 0 02 2 4 5 5 1M4 16 5 0 65 50 1 97 4 5 0 18 7 9 0 31 7 5 0 30 1 0 5 122 4 80...

Страница 22: ...Italy Tel 39 039 60531 Spain Mitsubishi Electric Europe B V Spanish Branch Carretera de Rubi 76 80 E 08190 Sant Cugat del Valles Barcelona Spain Tel 34 93 565 3131 France Mitsubishi Electric Europe B...

Отзывы: