10
-
21
CHAPTER10 CPU MODULE PROCESSING TIME
1
10
3
4
5
6
7
8
10.1 Scan T
ime
10.1.4
Factors that short
en the scan
time
(2) Floating-point operation processing ("Floating point arithmetic processing")
(
The time required for processing instructions that uses floating-point data can be shortened. To shorten the
processing time, deselect the "Perform internal arithmetic operations in double precision" item in the PLC system
tab of the PLC parameter dialog box.
Remark
For the operation processing time of the instruction that uses floating point data, refer to the following.
QCPU Programming Manual (Common Instructions)
Note3
Figure 10.7 Floating-point operation processing
Note10.3
The floating-point operation setting is not available for the Basic model QCPU, Process CPU, and Redundant CPU.
Basic
Process
Redundant
Deselect this item.