Start

Is power

LED lit?

• Check connection with the PC.

• Check power source of PC.

Is the send

data remainder

zero?

NO

YES

NO

Is send

wait flag M8121

turned on?

Is SD LED

(send) lit up

momentarily?

1

YES

Only receiving

fails to operate

normally

NO

 • Check the timing of control line.

 • Check the wiring of RS232C cable.
 • Check the wiring of control line.
 • Match the communication format.
 • Make sure the receiving external device is normal.
    (CR, LF may be needed in some printers.)
 • Check the data format of sending device.

YES

 • Check wiring of RS232C cable.

 • Check wiring of control line.

 • Make sure the receiving external device is normal.

 • Check the voltage level of RS232C signal (±9 V).

 • Make sure content of send data and communication format

are established before driving RS instruction.

NO

 • Check wiring of control line.

 • Check timing of send, receive.

 • Change RS instruction from OFF to ON.

 • Make sure the received data length matches with the receive

data area length.

NO

Is M8063

turned on?

 • There is a possibility of send crosstalk.  Check the send  and receive

timing with the external RS232C  device.

 • The receive data length may exceed the receive data area.

Check the receive data length and timing of receive start.

 • Check that the program is not set so that M8122 may be  always on.

 • Match the communication format.

 • Check the wiring of control line.

 • Check the start timing of send, receive.

No send
or receive
error

No send or receive error

Send,
receive
error

YES

NO

The data

transfer

complates

once.

NO

• Eliminate VRRD. VRSC

   instruction and reset power source.

NO

• Reset M8070, M8071, and

   reset power source.

YES

YES

Is VRRD

VRSC

instruction

used?

Are M8070,

M8071

turned on?

YES

}

Note: Only one of the following de-

vices can be connected to

the communications port on

the left of the PC:

FX-8AV, FX2-40AW,

FX2-40AP, FX-232ADP.

FX-485ADP

Содержание FX-232ADP

Страница 1: ...der in the correct installation and operation of the FX 232ADP and should be read and understood before attempting to install or use the unit Further information can be found in the FX SERIES PROGRAMM...

Страница 2: ...ted to the product RS232C connector Used for connection between the product and RS 232C device EXTERNAL DIMENSIONS TERMINAL LAYOUTS The connector is a 25 pin D SUB type and the pin configuration is as...

Страница 3: ...ase unit Related flag and data registers M8121 Send wait flag D8120 Communication format M8122 Send flag D8122 Remainder of send data M8123 Receive completion D8123 Number of received data M8124 Carri...

Страница 4: ...receive of data H138F 0001 0011 1000 1111 binary The settings for the above program are as right b0 b12 1 b11 0 SD TXD H W Ordinary mode Pin No ER DTR DR DSR When sending RD RXD ER DTR DR DSR When re...

Страница 5: ...2 ADP The connections of RS232C devices varies with each device being used Check the specification of the device and connect Connection examples Terminal specification device Modem specification devic...

Страница 6: ...D and LF H000A are written at the end of the message The printer moves down one line for each message CR Carriage Return LF Line Feed Note It may be necessary to set the DIP switches of your printer C...

Страница 7: ...software Use ordinary communication software terminal emulator or dedicated program in the personal computer The communication format of the PC for this example is as follows If the communication form...

Страница 8: ...is output to Y000 to Y017 When input X002 is turned on the receive completion flag is reset Personal computer operation Operation Sequence program M8000 M8161 M8002 X000 X001 M 0 MOV H0067 D8120 Sett...

Страница 9: ...ing Write the data to be sent to D 0 to D 19 before operating Send request Set the communication format according to the external device to be used M8002 M8000 M8013 M0 MOV H D8120 RS D0 K20 D100 K0 P...

Страница 10: ...line Check timing of send receive Change RS instruction from OFF to ON Make sure the received data length matches with the receive data area length NO Is M8063 turned on There is a possibility of sen...

Страница 11: ...the external sending device is sending the terminator Make sure the terminator value matches Match the communication format Check the timing of control line Check if the send data length is not zero w...

Страница 12: ...sponsible for any consequential damage that may arise as a result of the installation or use of this equipment All example and diagrams shown in this manual are intended only as an aid to understandin...

Отзывы: