Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
97
–
E59
E59-1, 2 *1
Compressor startup
failure (CM1,CM2)
Keeps flashing
Stays Off
Keeps flashing
*2
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis
Countermeasure
NO
NO
NO
YES
YES
YES
YES
Is
power supply voltage
OK?
specification of power supply
voltage
380/415V
Is the
pressure equalized
during 3-minute delay
before startup?
Is there
any loose connection
or breakage of cable
connected to the terminal
of the compressor?
Under the condition of no pressure difference,
startup by test operation mode
Check the data for 30 minutes before stopping
Save data for 30 minutes before stopping in Mente PC
Is it
the unit with one
compressor
?
Can startup?
Can startup?
Is there
any output from
inverter?
Is the
compressor failed to startup
switched?
YES
YES
YES
NO
NO
YES
YES (Both of 2 compressors can)
(Only one
compressor
can startup)
Interchange the
cables between
inverter and
compressor, and
try to startup
NO (No compressor can)
NO
NO
Check and save the data of
operating conditions
Check the power supply
voltage and correct it
Check the version No. of
software (Is it latest?)
Check whether the solenoid
valve SV6 at the exit of oil
separator is open during
compressor stopping.
(Is the pressure equalized?)
Replace the cable
(If there is a problem on
the terminal of compressor,
replace the compressor
Wait and see
Replace compressor
Replace inverter PCB or
power transistor module.
(Check 15V on the outdoor
control PCB and check
power transistor with inverter
checker.
If the power transistor is
OK, replace inverter PCB)
Replace compressor
Wait and see
Replace compressor
Replace inverter PCB or
power transistor module.
(Check 15V on the outdoor
control PCB and check power
transistor by inverter checker.
If the power transistor is
OK, replace inverter PCB)
2. Error detection method
When it fails to change over to
the operation for rotor position
detection of compressor motor
(If the compressor speed cannot
increase 11Hz or higher)
3.
Condition of error displayed
If the compressor fails to startup
for 20 times (10 patterns x 2
times) continuously.
4. Presumable cause
•
Anomalous voltage of power
supply
•
Anomalous components for
refrigerant circuit
•
Inverter PCB anomaly
•
Loose connection of
connector or cable
•
Compressor anomaly (Motor
or bearing)
Note: If the error does not recur, connect the Mente PC and continue to collect data.
*1 E59-1: CM1, E59-2: CM2 *2 E59-1: 1 time flash, E59-2: 2 time flash
Содержание FDE112KXE6A
Страница 104: ... 102 ...
Страница 106: ... 104 Table 1 Switch Setting Model JSW10 JSW11 1 2 3 4 All models INV1 OFF ON OFF OFF INV2 OFF ON OFF ON ...
Страница 110: ... 107 C PJF000Z053 3 ELECTRICAL WIRING 3 1 Indoor unit a Ceiling cassette 4 way type FDT Models All models ...
Страница 111: ... 108 b Ceiling cassette 4 way Compact type FDTC Models All moddels B PJA003Z331 ...
Страница 112: ... 109 c Ceiling cassette 2 way type FDTW Models FDTW28KXE6 45KXE6 56KXE6 B PJB001Z560 ...
Страница 113: ... 110 Models FDTW71KXE6 90KXE6 B PJB001Z561 ...
Страница 114: ... 111 Models FDTW112KXE6 140KXE6 B PJB001Z562 ...
Страница 115: ... 112 d Ceiling cassette 1 way type FDTS Model FDTS45KXE6 A PJC001Z195 ...
Страница 116: ... 113 Model FDTS71KXE6 A PJC001Z196 ...
Страница 117: ... 114 e Ceiling cassette 1 way compact type FDTQ Models All models A PJC001Z190 ...
Страница 118: ... 115 Models All models Duct panel A PJC001Z240 ...
Страница 120: ... 117 f Duct connected High static pressure type FDU Models 90KXE6 112KXE6 140KXE6 B PJD001Z229 ...
Страница 121: ... 118 Models FDU224KXE6 280KXE6 B PJD001Z230 ...
Страница 123: ... 120 Models FDUM112KXE6 140KXE6 B PJR002Z259 ...
Страница 124: ... 121 h Duct connected Ultra thin Low static pressure type FDQS Models All models C PJC001Z200 ...
Страница 125: ... 122 i Wall mounted type FDK Models FDK22KXE6 28KXE6 36KXE6 45KXE6 56KXE6 B PHA000Z983 ...
Страница 126: ... 123 Models FDK71KXE6 B PHA000Z984 ...
Страница 127: ... 124 j Ceiling suspended type FDE Models FDE36KXE6A 45KXE6A 56KXE6A B PFA003Z826 ...
Страница 128: ... 125 Models FDE71KXE6A 112KXE6A 140KXE6A B PFA003Z827 ...
Страница 129: ... 126 k Floor standing with casing type FDFL Models All models B PGD000Z053 ...
Страница 130: ... 127 l Floor standing without casing type FDFU Models All models A PGD000Z058 ...
Страница 131: ... 128 m Duct Connected Compact and Flexible type FDUH Models All models A PJC001Z255 ...
Страница 132: ... 129 3 2 Outdoor unit Models FDC335KXE6 K 400KXE6 450KXE6 504KXE6 560KXE6 560KXE6 K 615KXE6 680KXE6 PCB003Z060 ...
Страница 138: ... 135 ...
Страница 139: ... 136 ...
Страница 143: ... 140 b ...
Страница 144: ... 141 ...
Страница 191: ... 188 5 4 Installation of outdoor unit ...
Страница 193: ... 190 ...
Страница 194: ... 191 ...
Страница 195: ... 192 ...
Страница 196: ... 193 ...
Страница 197: ... 194 ...
Страница 198: ... 195 ...
Страница 199: ... 196 ...
Страница 200: ... 197 ...
Страница 201: ... 198 ...
Страница 202: ... 199 ...
Страница 203: ... 200 ...
Страница 204: ... 201 ...
Страница 205: ... 202 ...
Страница 206: ... 203 ...
Страница 207: ... 204 ...
Страница 208: ... 205 ...
Страница 210: ... 207 ...
Страница 211: ... 208 ...
Страница 212: ... 209 ...
Страница 215: ... 212 2 model type DIS model type HEAD ...
Страница 216: ... 213 2 2 ...
Страница 217: ... 214 2 2 2 2 2 ...