Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
69
–
E16
-
Indoor fan motor anomaly
(FDK series)
Keeps flashing 1 time flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
FDK series only
Diagnosis
Countermeasure
NO
YES
YES
Does any
foreign matter intervene
in rotational area of fan
impeller?
Is DC280V
detected between
①
-
③
of fan motor
connector CNM?
Does is become normal?
Does the fan
rotate smoothly when
turned by hand?
YES
NO
NO
NO
YES
(1)
Note (1)
③
for GND
Reset the power supply and restart.
Remove foreign matter.
Replace fan motor.
Replace fan motor and
power PCB
Replace fan motor. (If
this anomaly persists after
replacing the fan motor,
replace indoor control
PCB.)
Malfunction by temporary
noise
2. Error detection method
Detected by revolution speed of
indoor fan motor
3.
Condition of error displayed
When actual revolution speed of
indoor fan motor drops to lower
than 200min
-1
for 30 seconds
continuously, the compressor
and the indoor fan motor stop.
After 3-seconds delay, fan motor
starts again automatically, but
if this anomaly occurs 4 times
within 60 minutes after the
initial detection.
4. Presumable cause
• Indoor fan motor anomaly
• Foreign matter at rotational
area of fan impeller
• Fan motor anomaly
• Dust on control PCB
• Blown fuse
• External noise, surge
Note:
Содержание 112KXE6
Страница 104: ... 100 3 ELECTRICAL WIRING 3 1 Outdoor unit Models FDC224KXE6 280KXE6 A PCB003Z033 shows local wining ...
Страница 105: ... 101 Model FDC335KXE6 A PCB003Z035 shows local wining ...
Страница 134: ... 130 PJF012D003 ...
Страница 135: ... 131 ...
Страница 139: ... 135 PJA012D751 b ...
Страница 140: ... 136 ...
Страница 206: ... 202 2 model type DIS model type HEAD ...
Страница 207: ... 203 2 2 ...
Страница 208: ... 204 2 2 2 2 2 ...