58
OCH751
Switch
Type
of
switch
DIP
switch
Push
switch
SW1
1
2
No.
Function
Effective timing
Action by the switch operation
Manual defrost
*1
Start
Normal
When compressor is working
in heating operation.
*1
Abnormal history clear
Refrigerant address setting
When power supply ON
Clear
Normal
off or operating
SWP
6
5
4
3
Under suspension
Pump down
Start
Normal
SW4
1
2
Test run
Operating
OFF
Under suspension
Test run mode setting
Heating
Cooling
ON
OFF
1 2 3
0
1
2
3
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
4
5
6
7
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
8
9
10
11
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3
12
13
14
15
4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
1 2 3 4 5 6
ON
10-9. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS
(1) Function of switches
*1
Manual defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor
switch board
from OFF to ON.
2
Manual defrost will start by the above operation
1
if all these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost is finished.
• Pipe temperature is less than or equal to 8°C.
Manual defrost will finish if certain conditions have been satisfied.
Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
The black square (
) indicates a switch position.
Continue to the next page.