![Mitsubishi Electric WSH-ZM35I BEDRAAD SET Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/mitsubishi-electric/wsh-zm35i-bedraad-set/wsh-zm35i-bedraad-set_service-manual_1810102049.webp)
49
OCH751
10-5. HOW TO CHECK THE PARTS
Parts name
Checkpoints
Thermistor (TH3)
<Liquid>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<2-phase pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heat sink>
Thermistor (TH33)
<Comp. surface>
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10 to 30°C)
Normal
Abnormal
TH4, TH33
160 to 410 k
"
Open or short
TH3
TH6
TH7
4.3 to 9.6 k
"
TH8
39 to 105 k
"
Fan motor(MF1,MF2) Refer to the next page.
Solenoid valve coil
<4-way valve>
(21S4)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20°C)
Normal
Abnormal
2350±170
"
Open or short
Motor for compressor
(MC)
Measure the resistance between the terminals with a tester.
(Winding temperature at 20°C)
Normal
Abnormal
Refer to “5-2. COMPRESSOR TECHNICAL DATA”.
Open or short
Linear expansion valve
(LEV-A/LEV-B)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature at 20°C)
Normal
Abnormal
Red - White
Red - Orange
Red - Yellow
Red - Blue
Open or short
46±4
"
W
V
U
1
2
3
4
5
M
RD
BU
OG
YE
WH
Содержание WSH-ZM35I BEDRAAD SET
Страница 16: ...16 OCH751 6 OUTLINES AND DIMENSIONS Unit mm ...