Eng-11
- If you hear strange sounds, if no air is blown out or
if some other trouble occurs, switch off the power
and contact your dealer. Consult with your dealer
concerning the cost of inspection or repair work.
Consult with your dealer about the after-sales
services provided for this Lossnay product.
10. After-sales servicing
9. Specifications
Model
Supply
voltage (V)
Frequency
(Hz)
Notch
Power
consumption
(W)
Air volume
(m
3
/hr)
Temperature
exchange efficiency
(%)
Noise
(dB)
Weight
(kg)
VL-50S
2
-E
VL-50ES
2
-E
220
50
HI
19
51
70
36.5
6.2
LO
4
15
86
14
230
50
HI
20
52.5
69
37
LO
4.5
16
85
15
240
50
HI
21
54
68
37.5
LO
5.0
17
84
15.5
220
60
HI
21
54
68
37.5
LO
5.5
17
84
15.5
* Noise values may be higher than those listed depending on the structure of the room.
■ Retention period of functional repair parts
- We will retain the functional repair parts for six years after terminating production of the product.
- The functional repair part means a part which is necessary to maintain the function of the product.
■ Recommended inspection and maintenance
- After several years of use, the following might occur. We recommend inspection and maintenance
by a professional.
-
Entry of dust due to deterioration of filters
- Abnormal noise or vibration due to the motor reaching the end of its service life
-
Air leakage due to the heat exchanger Lossnay core reaching the end of its service life
The following are consumables:
- Motor
-
Supply air filter
-
Exhaust air filter
- Lossnay core
■ Repair costs include technical fee, cost of parts, (and business trip charges), etc.
Manufactured by:
TOKYO BLDG. 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO, 100-8310 JAPAN
Importer in EU: MITSUBISHI ELECTRIC EUROPE B.V.
HARMAN HOUSE, 1 GEORGE STREET, UXBRIDGE, MIDDLESEX, UB8 1QQ, U.K.