For the Air Curtain to be used for Weather Compensation Control (HEATING ECO
mode) with a PAR-W21MAA Remote Controller, the Heating Curve and Function
Limits must now be set-up as follows :-
Refer to PAR-W21MAA diagram, Figure 3, and typical heating curve in Figure 4 and
set up the Heating Curve:
1. Press button
I
to switch air curtain ON
2. Press button
E
to get ‘HEATING ECO’ mode
3. Press button
J
for 3 seconds, screen then says ‘LOADING’ for 30 secs
4. When ‘WATER TEMP HEATING’ is displayed on the screen press the
E
button to go to screen ‘WATER TEMP HEATING ECO no 1’
5. Use the
F
▼
or
▲
buttons to set the flashing Outdoor Air Temperature ‘Graph
Point
1
’ set this to
0°C
6. Press button
D
to make the Discharge Air Temperature flash at left of screen
7. Use the
F
▼
or
▲
buttons to set the flashing Discharge Air temperature
‘Graph Point
2
’ set this to
40°C
8. Press button
E
to go to screen ‘WATER TEMP HEATING ECO no 2’
9. Use the
F
▼
or
▲
buttons to set the flashing Outdoor Air temperature “Graph
Point
3
” set this to
15°C
10. Press button
D
to make the Discharge Air Temperature flash at left of screen
11. Use the
F
▼
or
▲
buttons to set the flashing Discharge Air Temperature
“Graph Point
4
” set this to
20°C
12. Press button
A
and screen then says ‘SETTING’ for 25s as the heating curve
program is written to the Interface PCB in the Air Curtain
13. Press button
I
to return to the ‘HEATING ECO’ screen
E
G
D
A
J
F
C
I
40°
C
Outdoor Air Temperature
(during heating curve set-up)
15°
C
Air Curtain
Discharge Air Temperature
(during heating curve set-up)
Figure 3
NB.
Read ‘Water Temperature’ on the screen as meaning ‘Air
Curtain Discharge Air temperature’ for this application