5. Refrigerant piping work

Fig. 5-2

Fig. 5-1

Fig. 5-3

5.1. Refrigerant pipe (Fig. 5-1)

► Check that the difference between the heights of the indoor and outdoor 

units, the length of refrigerant pipe, and the number of bends in the pipe 
are within the limits shown below.

Models

(A) Pipe length

(one way)

(B) Height 

difference

(C) Number of 

bends (one way)

SUZ-KA25/KA35

Max. 20 m

Max. 12 m

Max. of 10

SUZ-KA50/KA60/KA71

Max. 30 m

Max. 30 m 

Max. of 10

 

•  Height difference limitations are binding regardless of which unit, indoor or out-

door, is positioned higher.

•  Refrigerant  adjustment  ...  If  pipe  length  exceeds  7  m,  additional  refrigerant 

(R410A) charge is required.
(The outdoor unit is charged with refrigerant for pipe length up to 7 m.)

Pipe length

Up to 7 m

No additional charge is required.

Exceeding 7 m

Additional charge is required.
(Refer to the table below.)

Refrigerant 
to be added

SUZ-KA25/KA35 type 30 g × (refrigerant piping length (m) -7)
SUZ-KA50/KA60 type 20 g × (refrigerant piping length (m) -7)

SUZ-KA71 type

55 g × (refrigerant piping length (m) -7)

Piping preparation

•  Refrigerant pipes of 3, 5, 7, 10 and 15 m are available as optional items.

(1) Table below shows the specifications of pipes commercially available.

Model

Pipe

Outside diameter

Min. wall

thickness

Insulation

thickness

Insulation

material

mm

inch

SUZ-KA25

For liquid

6.35

1/4

0.8 mm

8 mm

Heat resisting 

foam plastic 

0.045 specific 

gravity

For gas

9.52

3/8

0.8 mm

8 mm

SUZ-KA35

For liquid

6.35

1/4

0.8 mm

8 mm

For gas

9.52

3/8

0.8 mm

8 mm

SUZ-KA50

For liquid

6.35

1/4

0.8 mm

8 mm

For gas

12.7

1/2

0.8 mm

8 mm

SUZ-KA60

For liquid

6.35

1/4

0.8 mm

8 mm

For gas

15.88

5/8

0.8 mm

8 mm

SUZ-KA71

For liquid

9.52

3/8

0.8 mm

8 mm

For gas

15.88

5/8

1.0 mm

8 mm

(2) Ensure that the 2 refrigerant pipes are well insulated to prevent condensation.
(3) Refrigerant pipe bending radius must be 100 mm or more.

 Caution:

Using careful insulation of specified thickness. Excessive thickness prevents 
storage behind the indoor unit and smaller thickness causes dew drippage.

5.2. Flaring work

•  Main cause of gas leakage is defect in flaring work.
  Carry out correct flaring work in the following procedure.

5.2.1. Pipe cutting (Fig. 5-3)

•  Using a pipe cutter cut the copper tube correctly.

5.2.2. Burrs removal (Fig. 5-4)

•  Completely remove all burrs from the cut cross section of pipe/tube.
•  Put the end of the copper tube/pipe to downward direction as you remove burrs 

in order to avoid burrs drop in the tubing.

5.2.3. Putting nut on (Fig. 5-5)

•  Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/

tube having completed burr removal.
(not possible to put them on after flaring work)

5.2.4. Flaring work (Fig. 5-6)

•  Carry out flaring work using flaring tool as shown at the right.

Pipe diameter

(mm)

Dimension

A (mm)

B

+0

    (mm)

-0.4

When the tool for R410A is used

Clutch type

6.35

0 - 0.5

9.1

9.52

0 - 0.5

13.2

12.7

0 - 0.5

16.6

15.88

0 - 0.5

19.7

Firmly hold copper tube in a die in the dimension shown in the table at above.

(C)

(B)

(A)

ø6.35

ø9.52

ø9.52

ø12.7

ø15.88

Fig. 5-4

Fig. 5-5

Fig. 5-6

 Indoor unit

 Outdoor unit

 Indoor unit

 Outdoor unit

/

 Copper tubes

0

 Good

1

 No good

2

 Tilted

3

 Uneven

4

 Burred

/

 Burr

0

 Copper tube/pipe

1

 Spare reamer

2

 Pipe cutter

/

 Flare nut

0

 Copper tube

/

 Flaring tool

0

 Die

1

 Copper tube

2

 Flare nut

3

 Yoke

Содержание SUZ-KA60VA3

Страница 1: ...lleren van de airconditioner begint MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore ...

Страница 2: ...relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than...

Страница 3: ...wind it is recommended to install a baffle board on the air outlet side of the outdoor unit Units should be installed by licensed contractor accordingly to local code re quirement Air outlet 2 10 mm 21 mm slot Air inlet 285 40 344 5 304 325 800 500 150 400 44 Drainage hole W42 In case of Heater models W33 69 Drain hose Drain socket 2 1 Fig 4 1 4 Drain piping for outdoor unit Fig 4 1 4 1 Accessorie...

Страница 4: ... 35 1 4 0 8 mm 8 mm For gas 12 7 1 2 0 8 mm 8 mm SUZ KA60 For liquid 6 35 1 4 0 8 mm 8 mm For gas 15 88 5 8 0 8 mm 8 mm SUZ KA71 For liquid 9 52 3 8 0 8 mm 8 mm For gas 15 88 5 8 1 0 mm 8 mm 2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation 3 Refrigerant pipe bending radius must be 100 mm or more Caution Using careful insulation of specified thickness Excessive thick...

Страница 5: ... the vacuum pump with the function to prevent the back flow Gauge manifold valve for R410A Pressure gauge for R410A Compound pressure gauge for R410A 0 101 MPa 760 mmHg Handle Low Handle High Window Charge hose for R410A Vacuum pump Adapter for preventing the back flow Charge hose for R410A Service port Stop valve PURGING PROCEDURES Connect the refrigerant pipes both the liquid and gas pipes betwe...

Страница 6: ...r cables Power supply cord Caution Use care not to make miswiring Firmly tighten the terminal screws to prevent then from loosening After tightening pull the wires lightly to confirm that they do not move Connect cable from the indoor unit correctly on the terminal block Use the same terminal block and polarity as is used with the indoor unit For aftercare maintenance give extra length to connecti...

Страница 7: ... 3 1 5 Polar 3 1 5 Polar 3 1 5 Polar Indoor unit Outdoor unit earth 1 Min 1 5 1 Min 1 5 1 Min 1 5 Circuit rating Outdoor unit L N 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S1 S2 2 AC 230 V AC 230 V AC 230 V Indoor unit Outdoor unit S2 S3 2 DC 12 V DC 24 V DC 12 V DC 24 V DC 12 V DC 24 V 1 A breaker with at least 3 mm contact separation in each poles shall be provided Use earth leakage ...

Страница 8: ...e be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy rela...

Отзывы: