39
OCH754A
10-4. TROUBLESHOOTING BY INFERIOR PHENOMENA
Phenomena
Factor
Countermeasure
1. Remote controller display does not
work.
2. “Please Wait” display is remained
on the remote controller.
3. When pressing the remote controller
operation switch the OPERATION
display is appeared but it will be
turned off soon.
1
After cancelling to select function from the remote
controller, the remote controller operation switch will
not be accepted for approx. 30 seconds.
1
Normal operation
1
At longest 2 minutes after the power supply “Please
Wait” is displayed to start up.
2
Communication error between the remote controller
and indoor unit
3
Communication error between the indoor and outdoor unit
4
Outdoor unit protection device connector is open.
1
12 VDC is not supplied to remote controller.
2
12–15 VDC is supplied to remote controller, however,
no display is indicated.
•
“Please Wait” is not displayed.
•
“Please Wait” is displayed.
1
Check LED2 on indoor controller board.
(1) When LED2 is lit:
check the remote controller wiring for
breaking or contact failure.
(2) When LED2 is blinking:
check short circuit of remote controller
wiring.
(3) When LED2 is not lit:
refer to No.3 below.
2
Check the following.
•
Failure of remote controller if “Please Wait”
is not displayed
•
Refer to No.2 below if “Please Wait” is dis-
played.
1
Normal operation
2
Self-diagnosis of remote controller
3
”Please Wait” is displayed for 6 min-
utes at most in the case of indoor/outdoor
unit communication error. Check LED3 on
indoor controller board.
(1)When LED3 is not blinking:
check indoor/outdoor connecting wire
for miswiring.
(Converse wiring of S1 and S2, or
break of S3 wiring.)
(2)When LED3 is blinking:
indoor/outdoor connecting wire is nor-
mal.
4
Check LED display on outdoor controller
circuit board. Refer to "10-9. FUNCTION
OF SWITCHES, CONNECTORS AND
JUMPERS".
Check protection device connector (63L
and 63H) for contact failure.
Refer to "10-8. TEST POINT DIAGRAM".
Abnormal point and detection method
Cause
Judgment and action
A8
(6608)
M-NET NO RESPONSE
Abnormal if a message was transmitted
and there were reply (ACK) that message
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, 6 times
continuously.
Note: The address and attribute displayed
at remote controller indicate the con-
troller that did not reply (ACK).
1
Transmitting condition is
repeated fault because of
noise and the like.
2
Voltage drop and weak signal
which lead communication
error are caused by over-range
transmission wire.
• Maximum distance··· 656 ft [ 200 m]
• Remote controller line(39 ft [12m])
3
Voltage drop and weak signal
which lead communication
error are caused by over-range
transmission wire.
Type····
With shield wire-
CVVS, CPEVS
With normal wire (no shield)-
VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····1.25 mm
2
[AWG16]
or more
4
Accidental malfunction of
abnormality-detected
controller
1
Check transmission waveform or noise on
transmission wire.
2
Turn off the power supply of outdoor unit
and indoor unit and FRESH MASTER or
LOSSNAY at the same time for 2 minutes or
more, and turn the power on again. If mal-
function was accidental, the unit returns to
normal. If the same abnormality occurs again,
controller of displayed address and attribute
may be defective.
Check Code
Содержание SUZ-KA24NAHZ
Страница 13: ...13 OCH754A 6 OUTLINES AND DIMENSIONS Unit mm in SUZ KA24NAHZ ...
Страница 14: ...14 OCH754A Unit mm in SUZ KA30NAHZ SUZ KA36NAHZ 1 1 1 ...
Страница 15: ...15 OCH754A 7 WIRING DIAGRAM SUZ KA24NAHZ ...
Страница 16: ...16 OCH754A SUZ KA30NAHZ SUZ KA36NAHZ ...