31
OCH754A
Abnormal point and detection method
Cause
Judgment and action
Check Code
Ud
(1504)
Overheat protection
Abnormal if outdoor pipe thermistor (TH3),
condensing temperature T
63HS
detects
158˚F [70
°C]
or more during compressor
operation.
1
Defective outdoor fan (fan
motor) or short cycle of outdoor
unit during cooling operation
2
Defective outdoor pipe thermis-
tor (TH3), condensing temper-
ture T
63HS
3
Defective outdoor controller board
1
Check outdoor unit air passage.
23
Turn the power off and on again to check
the check code. If U4 is displayed, follow the
U4 processing direction.
UE
(1302)
Abnormal pressure of 63HS
Abnormal if 63HS detects 14.5 PSIG [0.1
MPa] or less.
Detection is inoperative for 3 minutes after
compressor starting and 3 minutes after
and during defrosting.
63HS: High pressure sensor
1
Disconnection or contact
failure of connector (63HS) on
the outdoor controller circuit
board
2
Defective pressure sensor
3
Defective outdoor controller
circuit board
1
Check connection of connector (63HS) on
the outdoor controller circuit board.
Check breaking of the lead wire for 63HS.
2
Check pressure by microprocessor.
(Pressure sensor/ 63HS)
(SW2: Refer to "10-9. FUNCTION OF
SWITCHES, CONNECTORS AND
JUMPERS".)
3
Replace outdoor controller board.
UH
(5300)
Current sensor error
• It is abnormal for 38 A the input current or
10 seconds continuous 34 A or more.
1
Defective circuit of current
sensor on outdoor power circuit
board
2
Decrease of power supply
voltage
1
Replace outdoor power circuit board.
2
Check the facility of power supply.
UF
(4100)
Compressor overcurrent interruption
(When compressor locked)
Abnormal if overcurrent of DC bus or
compressor is detected within 30 seconds
after compressor starts operating.
10
PFC error (Overvoltage/
Undervoltage/Overcurrent)
• PFC detected any of the fol-
lowing:
a) Increase of DC bus voltage
as follows: 430 V
b) Decrease in PFC control
voltage to 13 VDC or lower
c) Increase in input current as
follows.
KA24: 42 A peak
KA30/36: 62 A peak
1
Abnormal increase in power
source voltage
2
Decrease in power source
voltage, instantaneous stop
3
Disconnection of compressor
wiring
4
Misconnection of reactor (DCL)
5
Defective outdoor power circuit
board
6
Defective reactor (DCL)
7
Disconnection or loose
connection of CN2 on the
outdoor power circuit board/
controller circuit board
12
Check the field facility for the power sup-
ply.
3
Correct the wiring (U·V·W phase) to
compressor. Refer to "10-8. TEST POINT
DIAGRAM".
4
Correct the wiring (U·V·W phase) or reactor
(DCL).
5
Replace outdoor power circuit board.
6
Replace reactor (DCL).
7
Check CN2 wiring.
08
Abnormal power synchronous
signal
• No input of power synchronous
signal to power circuit board
• Power synchronous signal
of 44 Hz or less, or 65 Hz or
more is detected on power
circuit board.
1
Distortion of power source
voltage, noise superimposition
2
Disconnection or loose
connection of earth wiring
3
Disconnection or loose
connection of CN2 on the
outdoor power circuit board /
controller circuit board
4
Defective power synchronous
signal circuit in outdoor
controller circuit board
5
Defective power synchronous
signal circuit in outdoor power
circuit board
1
Check the field facility for the power supply.
2
Check earth wiring.
3
Check CN2 wiring.
4
Replace outdoor controller circuit board.
5
Replace outdoor power circuit board.
U9
(4220)
1
Stop valve is closed.
2
Decrease of power supply
voltage
3
Looseness, disconnection or
converse of compressor wiring
connection
4
Defective compressor
5
Defective outdoor power board
6
DIP switch setting difference of
outdoor controller circuit board.
1
Open stop valve.
2
Check facility of power supply.
3
Correct the wiring (U
•
V
•
W phase) to
compressor. Refer to "10-8. TEST POINT
DIAGRAM" (Outdoor power circuit board).
4
Check compressor.
Refer to "10-5. HOW TO CHECK THE PARTS".
5
Replace outdoor power circuit board.
6
Check the dip switch setting of outdoor con-
troller circuit board. Refer to "Model Select" in
"1) Function of switches" in "10-9. FUNCTION
OF SWITCHES, CONNECTORS AND