'19 • PAC-SM-312
-
133
-
(2)
SRK series
Preset point of the protective devices
Parts name
Mark
Equipped unit
SRK series
Temperature sensor (for protection overloading in heating)
Th2
Indoor unit
OFF 51.5-58
℃ ,
ON 43-45
℃
Temperature sensor (for frost prevention)
OFF 2.5
℃ ,
ON 8
℃
Temperature sensor (for protection high pressure in cooling) TH1
Outdoor unit
OFF 62
℃ ,
ON 45-50
℃
Temperature sensor (for detecting discharge pipe temperature)
TH3
OFF 115
℃ ,
ON 95
℃
Indoor unit
Outdoor unit
Cooling cycle
Heating cycle
Heat
exchanger
temperature sensor
Heat
exchanger
temperature sensor
Room temperature
sensor
(Th3)
(Th1)
Humidity
sensor
(Th2
2
)
(Th2
1
)
Heat
exchanger
Gas pipe
(
φ
12.7)
Liquid pipe
(
φ
6.35)
Service valve
(Flare connecting)
Check joint
Service valve
(Flare connecting)
Electronic
expansion valve
Strainer
Receiver
Muffler
Capillary tube
Outdoor air
temperature sensor
Muffler
Compressor
Discharge pipe
temperature sensor
4way valve
(TH3)
(TH2)
Heat
exchanger
temperature sensor
(TH1)
(EEV)
Capillary tube
Heat
exchanger
Accumulator
Muffler
Reducer
(Accessory)
Model 71