'19 • PAC-SM-312
-
132
-
-
30
-
Indoor unit
Outdoor unit
Cooling cycle
Heating cycle
Temperature sensor
(Return air)
Temperature sensor
(Heat
exchanger)
(Thi-A)
(Thi-R1)
Temperature sensor
(Heat
exchanger)
(Thi-R3)
Temperature sensor
(Heat
exchanger)
(Thi-R2)
Heat
exchanger
Gas pipe
(
φ
12.7)
Liquid pipe
(
φ
6.35)
Service valve
(Flare connecting)
Check joint
Service valve
(Flare connecting)
Electronic
expansion valve
Strainer
Receiver
Strainer
Capillary tube
Outdoor air
temperature sensor
Muffler
Compressor
Discharge pipe
temperature sensor
4-way valve
(TH3)
(TH2)
Heat
exchanger
temperature sensor
(TH1)
(EEV)
Capillary tube
Heat
exchanger
Accumulator
Muffler
Reducer
(Accessory)
Reducer
(Accessory)
4. PIPING SYSTEM
Preset point of the protective devices
Parts name
Mark
Equipped unit
FDT, FDU, FDUM, FDE series
Temperature sensor (for protection overloading in heating)
Thi-R
Indoor unit
OFF 63
℃ ,
ON 56
℃
Temperature sensor (for frost prevention)
OFF 1.0
℃ ,
ON 10
℃
Temperature sensor (for protection high pressure in cooling) TH1
Outdoor unit
OFF 62
℃ ,
Temperature sensor (for detecting discharge pipe temperature) TH3
OFF 115
℃ ,
ON 95
℃
(1)
FDT, FDU, FDUM, FDE series
ON 45-50
℃