background image

8

7. Electrical work

7.3. Remote controller

7.3.1. For wired remote controller

1) Installing procedures

(1) Select an installing position for the remote controller. (Fig. 7-4)
The temperature sensors are located on both remote controller and indoor unit.

s

Procure the following parts locally:

Two piece switch box
Thin copper conduit tube
Lock nuts and bushings

A

Remote controller profile

B

Required clearances surrounding the remote controller

C

Installation pitch

(2) Seal the service entrance for the remote controller cord with putty to prevent

possible invasion of dew drops, water, cockroaches or worms. (Fig. 7-5)

A

For installation in the switch box:

B

For direct installation on the wall select one of the following:

• Prepare a hole through the wall to pass the remote controller cord (in order to run

the remote controller cord from the back), then seal the hole with putty.

• Run the remote controller cord through the cutout in the upper case, then seal the

cutout notch with putty similarly as above.

B-1. To lead the remote controller cord from the back of the controller:
B-2. To run the remote controller cord through the upper portion:

(3) For direct installation on the wall

C

Wall

G

Switch box

D

Conduit

H

Remote controller cord

E

Lock nut

I

Seal with putty

F

Bushing

J

Wood screw

2) Connecting procedures (Fig. 7-6)

1

Connect the remote controller cord to the terminal block.

A

To the terminal block on the indoor unit

B

TB6 (No polarity)

2

Set the dip switch No.1 shown below when using two remote controller’s for the
same group.

C

Dip switches

3) Function selection of remote controller

If two remote controllers are connected, set one to “Main” and the other to “Sub”. For
setting procedures, refer to “Function selection of remote controller” in the operation
manual for the indoor unit.

7.4. Function settings

7.4.1 Function setting on the unit (Selecting the unit functions)

1) AUTO RESTART FUNCTION
Indoor controller board

This model is equipped with the AUTO RESTART FUNCTION.
(the DIP switch on the indoor controller board)
When the indoor unit is controlled with the remote controller, the operation mode, set
temperature, and the fan speed are memorized by the indoor controller board. The
auto restart function sets to work the moment the power has restored after power
failure, then, the unit will restart automatically.

OFF : Not available
ON : Available (Initial setting)

* When the power supply returns, the air conditioner will start 3 minutes later.

2) Other functions
For wired remote controller only (Fig. 7-7)

Changing the power voltage setting
• Be sure to change the power voltage setting depending on the voltage used.

1

Go to the function setting mode.

Switch OFF the remote controller.
Press the 

A

 and 

B

 buttons simultaneously and hold  them for at least 2

seconds. FUNCTION will start to flash.

2

Use the 

C

 button to set the refrigerant address (

3

) to 00.

3

Press 

D

 and [--] will start to flash in the unit number (

4

) display.

4

Use the 

C

 button to set the unit number (

4

) to 00.

5

Press the 

E

 MODE button to designate the refrigerant address/unit number. [--]

will flash in the mode number (

1

) display momentarily.

6

Press the 

F

 buttons to set the mode number (

1

) to 04.

7

Press the 

G

 button and the current set setting number (

2

) will flash.

Use the 

F

 button to switch the setting number in response to the power supply

voltage to be used.
Power supply voltage

240 V

: setting number = 1

220 V, 230 V : setting number = 2

8

Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will

change to being on constantly and the contents of the setting can be confirmed.

9

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least two

seconds. The function selection screen will disappear momentarily and the air
conditioner OFF display will appear.

30

46

30

30

120

83.5

A

B

C

F

A

H

C

D

E

G

I

I

I

H

B

B-1.

B-2.

Fig. 7-5

A

AB

TB6

B

Fig. 7-4

Fig. 7-6

J

H

PAR-21MAA

ON/OFF 

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

A

B

D

C

G

E

F

4

1

2

1

3 4

1

2

Fig. 7-7

Mode number

Setting number

Refrigerant address

Unit number

1

2

3

4

ON
OFF

1

5

2

SW3

3 4

Power failure automatic recovery

Содержание SEZ-KA50

Страница 1: ...ad this manual and outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈÓ fi ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÙÈÎÔ POUR L INSTALLATEUR ...

Страница 2: ... electrical work according to the installation manual and be sure to use an exclusive circuit If the capacity of the power circuit is insufficient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the serv...

Страница 3: ...llation remove the transportation support PLATE B I PLATE B 2 J Inlet size A Air inlet bottom side dimensions PLATE A 24 ø2 9 holes 2 2 ø2 9 holes 20 or more 24 ø2 9 holes Air inlet rear side dimensions 9 2 ø2 9 holes 8 3 2 5 7 A 1070 270 30 1100 25 75 32 5 10 50 94 60 350 100 108 25 20 170 A F B C D 2 E A B 1 2 3 Fig 3 2 3 2 Checking the indoor unit accessories Fig 3 2 Check that the indoor unit ...

Страница 4: ... B A A A B C D 350 1070 Fig 4 1 Fig 4 3 Fig 4 4 Fig 4 2 4 3 Transportation support removal Fig 4 4 After installation completely remove the transportation support because this part should only be used during transportation A 3 screws B Transportation support 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional it...

Страница 5: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 6: ... air conditioner installation Label each breaker according to purpose heater unit etc Fig 7 1 A Indoor unit B Outdoor unit C Wired remote controller D Main switch fuse E Grounding For Power supply For Power supply A C B D S3 S3 S2 S1 S2 S1 2 1 D E C B A A A 1 SEZ KA35 KA50 KA60 KA71VA 6 Drainage piping work Fig 6 1 6 1 Drainage pipe connection Fig 6 1 Indoor unit s drainage pipe The drainage pipe ...

Страница 7: ...or unit s fan motor is for a 50 Hz power supply The wiring must be reconfigured if a 60 Hz power supply is used Refer to the wiring diagram for details 1 Entry for wired remote controller cable 2 Entry for Indoor Outdoor connecting cable 3 Cable clamp 4 Remote controller terminal 5 Indoor Outdoor unit connecting terminal 6 To wired remote controller 7 To outdoor unit 8 Indoor controller 9 Power bo...

Страница 8: ...with the AUTO RESTART FUNCTION the DIP switch on the indoor controller board When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor controller board The auto restart function sets to work the moment the power has restored after power failure then the unit will restart automatically OFF Not available ON Availabl...

Страница 9: ...ctions Not supported Supported No vanes Equipped with vanes vanes angle setup 1 Equipped with vanes vanes angle setup 2 Disabled Enabled Mode no Setting no Initial setting Setting 1 07 2 3 1 08 2 3 1 09 2 3 10 1 2 11 1 2 3 12 1 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller 1 For this model mode no 1 cannot be set using the remote controller Se...

Страница 10: ...er 1 E Rail 2 F Rail 3 G Bend H Clamp 5 A A 5 4 C C 4 3 5 6 2 1 Fig 8 3 8 3 Filter rail installation Bottom air intake Fig 8 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please attach filter rail 2 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Please attach filter rail 3 as per the diagram screw 6 Please connect rai...

Страница 11: ... Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malf...

Страница 12: ...ecified refrigerant address is incorrect Check code displayed in the LCD For details check the LED display of the outdoor controller board 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection butt...

Страница 13: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79U787H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: