background image

5

a

d

c

b

e

f

90

°

d

c

b

a

5. Refrigerant piping work

b

a

a

b

e

b

c

d

c

A

5.2. Flaring work

• Main cause of gas leakage is defect in flaring work.

Carry out correct flaring work in the following procedure.

5.2.1. Pipe cutting (Fig. 5-2)

• Using a pipe cutter cut the copper tube correctly.

5.2.2. Burrs removal (Fig. 5-3)

• Completely remove all burrs from the cut cross section of pipe/tube.
• Put the end of the copper tube/pipe to downward direction as you remove burrs in

order to avoid burrs drop in the tubing.

5.2.3. Putting nut on (Fig. 5-4)

• Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube

having completed burr removal.
(not possible to put them on after flaring work)

5.2.4. Flaring work (Fig. 5-5)

• Carry out flaring work using flaring tool as shown at the right.

Dimension

Pipe diameter

A (mm)

(mm)

When the tool for R410A is used

B       (mm)

Clutch type

6.35

0 - 0.5

9.1

9.52

0 - 0.5

13.2

12.7

0 - 0.5

16.6

15.88

0 - 0.5

19.7

Firmly hold copper tube in a die in the dimension shown in the table at above.

5.2.5. Check (Fig. 5-6)

• Compare the flared work with a figure in right side hand.
• If flare is noted to be defective, cut off the flared section and do flaring work again.

5.3. Pipe connection (Fig.5-7)

• Apply a thin coat of refrigeration oil on the seat surface of pipe.
• For connection first align the center, then tighten the first 3 to 4 turns of flare nut.
• Use tightening torque table below as a guideline for indoor unit side union joint section,

and tighten using two wrenches. Excessive tightening damages the flare section.

Copper pipe O.D.

Flare nut O.D.

Tightening torque

(mm)

(mm)

 (N·m)

ø6.35

17

14 - 18

ø9.52

22

34 - 42

ø12.7

26

49 - 61

ø15.88

29

68 - 82

 Warning:

Be careful of flying flare nut! (Internally pressurized)
Remove the flare nut as follows:
1. Loosen the nut until you hear a hissing noise.
2. Do not remove the nut until the gas has been completely released (i.e., hiss-

ing noise stops).

3. Check that the gas has been completely released, and then remove the nut.

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit in the same manner applied
for indoor unit.
• For tightening use a torque wrench or spanner, and use the same tightening torque

applied for indoor unit.

Refrigerant pipe insulation (Fig. 5-8)

(1) Peel the separator sheet off the accompanying pipe cover, and wrap it around the

refrigerant pipe, making sure that the side which is slit faces upwards.

(2) Be sure to fix both ends of the pipe cover using an attachment band (ensure that

the band’s joint faces upwards).

(3) Stick vinyl tape on the joint positions.

a

Copper tubes

b

Good

c

No good

d

Tilted

e

Uneven

f

Burred

Fig. 5-2

Fig. 5-3

a

Burr

b

Copper tube/pipe

c

Spare reamer

d

Pipe cutter

Fig. 5-4

Fig. 5-5

Fig. 5-6

Fig. 5-7

Fig. 5-8

a

Flare nut

b

Copper tube

a

Flaring tool

b

Die

c

Copper tube

d

Flare nut

e

Yoke

a

f c b

d

e

b

c e

g

h

c

i

a

Indoor unit (main unit)

b

1 Pipe cover

c

2 Band

d

Flare joint

e

Refrigerant pipe and insulating ma-
terial (must be supplied locally)

f

Position the pipe cover so that the end
is in firm contact with the main unit.
Fasten it so that there is no clearance.

g

Allow no clearance

h

Separator sheet

i

Cut off the remainder band

a

Smooth all around

b

Inside is shining without any scratches

c

Even length all around

d

Too much

e

Tilted

f

Scratch on flared plane

g

Cracked

h

Uneven

i

Bad examples

c

b

a

d

e

f

g

h

i

B

+0

-0.4

Содержание SEZ-KA50

Страница 1: ...ad this manual and outdoor unit installation manual thoroughly before installing the air conditioner unit FOR INSTALLER E XEIPI IO O H IøN E KATA TA H È ÛˆÛÙ Î È ÛÊ Ï Ú ÛË È ÛÙ ÚÔÛÂÎÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ Î ıÒ Î È ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÙË Â͈ÙÂÚÈÎ ÌÔÓ ÚÈÓ fi ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÙÈÎÔ POUR L INSTALLATEUR ...

Страница 2: ... electrical work according to the installation manual and be sure to use an exclusive circuit If the capacity of the power circuit is insufficient or there is incomplete elec trical work it could result in a fire or an electric shock Attach the electrical part cover to the indoor unit and the service panel to the outdoor unit securely If the electrical part cover in the indoor unit and or the serv...

Страница 3: ...llation remove the transportation support PLATE B I PLATE B 2 J Inlet size A Air inlet bottom side dimensions PLATE A 24 ø2 9 holes 2 2 ø2 9 holes 20 or more 24 ø2 9 holes Air inlet rear side dimensions 9 2 ø2 9 holes 8 3 2 5 7 A 1070 270 30 1100 25 75 32 5 10 50 94 60 350 100 108 25 20 170 A F B C D 2 E A B 1 2 3 Fig 3 2 3 2 Checking the indoor unit accessories Fig 3 2 Check that the indoor unit ...

Страница 4: ... B A A A B C D 350 1070 Fig 4 1 Fig 4 3 Fig 4 4 Fig 4 2 4 3 Transportation support removal Fig 4 4 After installation completely remove the transportation support because this part should only be used during transportation A 3 screws B Transportation support 5 Refrigerant piping work 5 1 Refrigerant pipe Fig 5 1 Piping preparation Refrigerant pipes of 3 5 7 10 and 15 m are available as optional it...

Страница 5: ... torque mm mm N m ø6 35 17 14 18 ø9 52 22 34 42 ø12 7 26 49 61 ø15 88 29 68 82 Warning Be careful of flying flare nut Internally pressurized Remove the flare nut as follows 1 Loosen the nut until you hear a hissing noise 2 Do not remove the nut until the gas has been completely released i e hiss ing noise stops 3 Check that the gas has been completely released and then remove the nut Outdoor unit ...

Страница 6: ... air conditioner installation Label each breaker according to purpose heater unit etc Fig 7 1 A Indoor unit B Outdoor unit C Wired remote controller D Main switch fuse E Grounding For Power supply For Power supply A C B D S3 S3 S2 S1 S2 S1 2 1 D E C B A A A 1 SEZ KA35 KA50 KA60 KA71VA 6 Drainage piping work Fig 6 1 6 1 Drainage pipe connection Fig 6 1 Indoor unit s drainage pipe The drainage pipe ...

Страница 7: ...or unit s fan motor is for a 50 Hz power supply The wiring must be reconfigured if a 60 Hz power supply is used Refer to the wiring diagram for details 1 Entry for wired remote controller cable 2 Entry for Indoor Outdoor connecting cable 3 Cable clamp 4 Remote controller terminal 5 Indoor Outdoor unit connecting terminal 6 To wired remote controller 7 To outdoor unit 8 Indoor controller 9 Power bo...

Страница 8: ...with the AUTO RESTART FUNCTION the DIP switch on the indoor controller board When the indoor unit is controlled with the remote controller the operation mode set temperature and the fan speed are memorized by the indoor controller board The auto restart function sets to work the moment the power has restored after power failure then the unit will restart automatically OFF Not available ON Availabl...

Страница 9: ...ctions Not supported Supported No vanes Equipped with vanes vanes angle setup 1 Equipped with vanes vanes angle setup 2 Disabled Enabled Mode no Setting no Initial setting Setting 1 07 2 3 1 08 2 3 1 09 2 3 10 1 2 11 1 2 3 12 1 2 Select unit numbers 01 to 03 or all units AL wired remote controller 07 wireless remote controller 1 For this model mode no 1 cannot be set using the remote controller Se...

Страница 10: ...er 1 E Rail 2 F Rail 3 G Bend H Clamp 5 A A 5 4 C C 4 3 5 6 2 1 Fig 8 3 8 3 Filter rail installation Bottom air intake Fig 8 3 1 Transportation support remove Throw away 2 Please move the plate position Please use the screws removed 3 Please attach filter rail 2 as per the diagram screw 6 Please connect rails 2 3 carefully 4 Please attach filter rail 3 as per the diagram screw 6 Please connect rai...

Страница 11: ... Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Insulation resistance After installation or after the power source to the unit has been cut for an extended period the insulation resistance will drop below 1 MΩ due to refrigerant accumulat ing in the compressor This is not a malf...

Страница 12: ...ecified refrigerant address is incorrect Check code displayed in the LCD For details check the LED display of the outdoor controller board 10 Test run 10 2 Test run The following 3 methods are available 10 2 1 Using wired remote controller Fig 10 1 1 Turn on the power at least 12 hours before the test run 2 Press the TEST button twice TEST RUN liquid crystal display 3 Press the Mode selection butt...

Страница 13: ...EC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN BG79U787H01 The product at hand is based on the following EU regulations Printed in Thailand ...

Отзывы: