47
PEAD-RP60GA PEAD-RP71GA
Capacity cord
switch
Model selection
switch
SW2
SW1
ON
OFF
1 2 3 4 5
ON
OFF
1 2 3 4 5
5
4
3
2
1
OFF
ON
71GA
60GA
MODELS
TO MA-REMOTE
CONTROLLER
DC8.7-13V
TO OUTDOOR UNIT
X6
X5
X4
X1
ZNR
FUSE
P.B.
I.B.
X1
Y
L
W
O
R
N
X6
X5
X4
2
1
(RED)
(WHT)
(WHT)
(YLW)
(WHT)
(WHT)
(WHT)
B
L
U
B
L
U
B
L
U
B
L
U
(BLK)
(WHT)
(RED)
(BLU)
B
L
K
W
H
T
BLK
WHT
(WHT)
(BLU)
B
R
N
BRN
O
R
N
ORN
YLW
(BLU)
(RED)
(ORN)
(RED)
(WHT)
B
L
K
W
H
T
B
L
K
W
H
T
(WHT)
(WHT)
O
R
G
B
L
K
B
L
U
B
L
K
Y
L
W
Y
L
W
G
R
Y
*
(FACTORY SHIPMENT)
240V
230V
220V
20Pa
60Pa
75Pa
10Pa
50Pa
70Pa
50Pa
35Pa
5Pa
RED
WHT
BLU
CONNECTOR COLOR
2
1
TB5
TB4
S3
S1
S2
2
1
CNP
1
3
3
1
3
1
1
3
CNSK
2 1
CN2S
6
4
3
5
2
1
MF
C
1 2
CN24
3
2
1
1 2 3
1 2
1 2
1 2
TH5
TH2
TH1
LED1
LED2
LED3
1
2
CN2D
CN3C
3
1
CND
CNDK
1
3
7
FAN
5
OFF
ON
SWE
SW2
SW1
CN2L
CN22
CN20
CN21
CN29
CN31
CN90
CN41
CN51
CN32
2
1
1 2 3 4 5 6 7 8 9
4
3
2
1
5
4
3
2
1
INSIDE SECTION OF CONTROL BOX
*External static pressure
RELAY(DRAIN PUMP)
X1
CONNECTOR(WIRELESS)
TRANSMISSION(INDOOR•OUTDOOR)
LED3
POWER SUPPLY(REMOTE CONTROLLER)
LED2
LED1 POWER SUPPLY(I.B.)
CN90
CN51 CONNECTOR(CENTRALLY CONTROL)
CN24 CONNECTOR(HEATER)
VARISTOR
FUSE(T6.3AL250V)
ZNR
FUSE
INDOOR POWER BOARD
P.B.
COND./EVA. TEMP. THERMISTOR
(0
/15
k
Ω
, 25
/5.4
k
Ω
DETECT)
PIPE TEMP. THERMISTOR/LIQUID
(0
/15
k
Ω
, 25
/5.4
k
Ω
DETECT)
INTAKE AIR TEMP.THERMISTOR
(0
/15
k
Ω
, 25
/5.4
k
Ω
DETECT)
TERMINAL BLOCK
(INDOOR/OUTDOOR CONNECTING LINE)
TERMINAL BLOCK(REMOTE CONTROLLER)
FAN MOTOR
CAPACITOR(FAN MOTOR)
TH5
TH2
TH1
TB4
TB5
MF
C
NAME
NAME
SYMBOL
SYMBOL
NAME
[LEGEND]
RELAY(FAN MOTOR)
RELAY(FAN MOTOR)
SWITCH(CAPACITY CODE)
CONNECTOR(HA TERMINAL-A)
CONNECTOR(REMOTE SWITCH)
INDOOR CONTROLLER BOARD
RELAY(FAN MOTOR)
SWITCH(EMERGENCY OPERATION)
SWITCH(MODEL SELECTION)
CONNECTOR(LOSSNAY)
X6
X5
X4
SWE
SW2
SW1
CN41
CN32
CN2L
I.B.
SYMBOL
NOTES:
1. Since the outdoor side electric wiring may change, be sure to check the outdoor
unit electric wiring diagram for servicing.
2. Indoor and outdoor connecting wires have poIarities, make sure to match
terminal numbers (S1, S2, S3) for correct wirings.
3. Symbols used in wiring diagram above are,
: Connector, : Terminal (block).
4. The wiring between MA-Remote controller and TB5 is included in the package.