14
Model name
Indoor unit
PEA-RP71EA
Outdoor unit
SUZ-KA71VA
Cooling
Capacity
Btu/h
23,500
kW
6.9
Total input
kW
2.90
EER
2.38
SHF
0.84
Heating
Capacity
Btu/h
27,300
kW
8.0
Total input
kW
2.49
COP
3.21
Booster heater
kW
—
Power supply
Phase
:
1
Cycle
Hz
50
Voltage
V
230
Breaker size
A
20
Indoor unit
Air flow
CMM
22 - 27
(Low - High)
R/s
367 - 450
External static pressure
Pa
125
Sound level
dB(A)
52 - 55
(Low - High)
External finish
Galvanized sheets
Dimension
W : mm
785
D : mm
690
H : mm
428
W : inch
31
D : inch
27 - 1/16
H : inch
16 - 7/8
Weight
kg
46
lbs
101
Unit drain pipe
R1(External thread)
Outdoor unit
Air flow at cooling
CMM
27.5 - 49
(Low - High)
CFM
970 - 1,730
Air flow at heating
CMM
36.8 - 49
(Low - High)
CFM
1,300 - 1,730
Sound level at cooling
dB(A)
51 - 53
(Low - High)
Sound level at heating
dB(A)
53 - 55
(Low - High)
External finish
Ivory Munsell 3.0Y 7.8/1.1
Dimension
W : mm
840
D : mm
330
H : mm
850
W : inch
33 - 1/16
D : inch
13
H : inch
33 - 7/16
Weight
kg
58
lbs
128
Refrigerant pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Length
m
Max. 30
NOTE:
1.
Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
(80°F) W.B. 19
(66°F)
Outdoor : D.B. 35
(95°F) W.B. 24
(75°F)
Heating Indoor : D.B. 20
(68°F)
Outdoor : D.B. 7
(45°F)
W.B. 6
(43°F)
Refrigerant piping length (one way) : 5m (16ft.)
2.
Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit
32°C D.B. , 23°C W.B.
43°C D.B.
KA71
Lower limit
21°C D.B. , 15°C W.B.
-15°C D.B.
Heating
Upper limit
27°C D.B.
24°C D.B. , 18°C W.B.
Lower limit
20°C D.B.
-10°C D.B. ,-11°C W.B.
4.
Above data are based on the indicated voltage.
Indoor unit
Single phase, 230V 50Hz
Single phase, 230V 50Hz
Outdoor unit
3.
Guaranteed voltage
198~264V, 50Hz